 OBSOLETE HONEYWELL W9076A1000 Digital Temperature indicator that provides a continuous LED display for temperature (includes sensor). The W9076 digital temperature indicator provides continuous led (light-emitting diode) digital display of temperature in commercial building applications. Display permits user selection of fahrenheit or celsius readings in the range of -40 F to 199 F (-40 C to 93 C). Several locations can be monitored on the display through suitable switching of additional remote sensors.
Features Fahrenheit or Celsius display is field selectable. Solid state sensor provides fast response, accurate temperature readings. The 3-1/2 digit LED display has 0.3 inch numerals. Front mounting permits fast, easy installation.
Product Specifications
Description: Digital Temperature indicator that provides a continuous LED display for temperature (includes sensor)
Application: Monitors temperature is space or ducts, and fluid in hot or cold water pipes
Contact Ratings: 49 mm dia, 70mm long
Voltage: 24 Vac, +25%, -15%. For each volt above 26 Vac, derate ambient temperature by 5 F (2.8 C)
Frequency: 60 Hz
Frequency: 50 Hz
Operating Temperature Range (F): -40 F to +199 F
Operating Temperature Range (C): -40 C to +93 C
Dimensions (in.): 4 9/16 in. high x 1 15/16 wide x 2 3/4 in. deep
Dimensions (mm): 116 mm high x 49 mm wide x 70 mm deep
Includes: 194950E Sensor
Comments: Solid state sensor usable up to 300 ft (91 m)
Used With: T7047C1090 Case (for wall mounting the remote sensor), 121371A Immersion Well, 131524A/107324A/311266D Holders for duct mounting sensor, 107408 Heat-inductive compound
|