 Honeywell RA890F1270, 120 Vac Protectorelayฎ with 0.8 second flame failure response time and 15 second safety switch timing. Primary control provides solid state, electronic flame safeguard protection for industrial and commercial single or dual fuel burners for rectification type flame detection.
Features
Uses rectification principle of electronic flame detection.
Replaces RA890E in most applications and mounts on same Q270A1024 Subbase.
Recycles if flame signal lost while in Run. Failure to establish pilot results in a lockout.
Safe-start check prevents start-up if flame-simulating failure occurs in flame detector circuit.
Includes built-in protection against ignition crossover in flame rod systems.
Includes SPDT alarm contacts.
Solid state circuitry.
Mounts and removes easily through use of captive mounting screws.
Mounting base is made of strong thermoplastic.
Product Specifications
Description: Rectification, with alarm contacts
Application: Primary control for rectification application (Flame Rod for example)
Flame Failure Response Time (sec): 0.8 sec
Safety Switch Timing: 15 seconds
Voltage: 120 Vac
Frequency: 50 Hz
Frequency: 60 Hz
Alarm Relay Switching: SPDT
Temperature Range (F): 50 Hz models -20 F to +105 F
Temperature Range (F): 60 Hz models -20 F to +115 F
Temperature Range (C): 50 Hz Models -29 C to +41 C
Temperature Range (C): 60 Hz Models -29 C to +46 C
Dimensions (in.): 5 in. high x 5 in. wide x 4 3/4 in. deep (including subbase)
Dimensions (mm): 127 mm high x 127 mm wide x 121 mm deep (including subbase)
Approvals, Underwriters Laboratories Inc - UL Listed: 120V models only; File No. MP268, Guide No. MCCZ
Approvals, Canadian Standards Association - CSA Certified: 120V models only; File No. LR1620
Approvals, Factory Mutual - Approved: Report No. 17678,19417,19784
|