Honeywell R7140M2005 Computerized Burner Control - Upgrade Replacement Programming Control for BC7000L with PM720L. The Honeywell R7140G, L, M Burner Control Modules are microprocessor-based integrated burner control for automatically fired gas, oil or combination fuel single burner applications.
Features:
Functions provided by the R7140G,L,M include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting.
Require ST7800 Purge Timer and appropriate R78XX Amplifier to complete the replacement.
Flame Establishing Period - Pilot: 4 sec or 10 sec
Flame Establishing Period - Main: 10 sec, 15 sec
Interlocks: Lockout
Preignition: Yes
PrePurge: Determined by ST7800A Purge Timer Card
PostPurge: 15 sec
Required Components: R7847, R7848, R7849, R7851, R7861, or R7886 Flame Signal Amplifier. ST7800 Plug-in Purge Timer Card.
Voltage: 120 Vac (+10, -15%)
Frequency: 50 Hz
Frequency: 60 Hz (±10%)
AirFlow Check: User selectable
Pilot Type: Interrupted
Vibration: 0.5 G environment
Early Spark Termination: Yes, 5 sec
Ambient Temperature Range (F): -40 F to +140 F
Ambient Temperature Range (C): -40 C to +60 C
Dimensions (in.): 7 in. wide x 6 5/32 high x 5 3/4 in. deep
Dimensions (mm): 177 mm wide x 156 mm high x 146 mm deep
Weight (lb): 3 lb 1 oz
Weight (kg): 1.4 kg
Approvals, Underwriters Laboratories Inc: Component Recognized, File No. MP268; Guide No. MCCZ.
Approvals, Federal Communications Commission: FCC Part 15, Class B, Emissions.
Comments: LHL-LF Proven
|