Honeywell R7120M1019 Microprocessor Relay Module - Replacement Primary Control for Fireye M Series - Interrupted Pilot. The Honeywell R7120M Burner Control Modules are microprocessor-based integrated burner controls. It is a plug in replacement of Fireye M series controls for automatically fired gas, oil or combination fuel on/off single burner applications.
Features:
Functions provided by the R7120M include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting.
Plug in replacement for Fireye M series controls using the existing Fireye wiring subbase.
Require ST7800 Purge Timer and appropriate R78XX Amplifier to complete the replacement.
Product Specifications:
Application: Replacement Primary Control for Fireye M Series - Intermittent Pilot
Flame Establishing Period - Pilot: 4 sec or 10 sec
Flame Establishing Period - Main: Intermittent
Interlocks: Running
PrePurge: Determined by ST7800A Purge Timer Card
PostPurge: Programmed with S7800A1142 display
Required Components: R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800 Plug-in Purge Timer Card.
Voltage: 120 Vac (+10, -15%)
Frequency: 50 Hz; 60 Hz
AirFlow Check: User selectable
Pilot Type: intermittent
Vibration: 0.5 G environment
Ambient Temperature Range (F): -40 F to +135 F
Ambient Temperature Range (C): -40 C to +57 C
Dimensions (in.): 7 in. wide x 6 5/32 high x 5 3/4 in. deep
Dimensions (mm): 177 mm wide x 156 mm high x 146 mm deep
Weight (lb): 3 lb 1 oz
Weight (kg): 1.4 kg
Approvals, Underwriters Laboratories Inc: Component Recognized, File No. MP268; Guide No. MCCZ.
Approvals, Federal Communications Commission: FCC Part 15, Class B, Emissions.
|