HONEYWELL L404F1375 Pressuretrol Controller, Auto recycle, 5 psi to 50 psi. Provide operating control, automatic or manual reset limit protection for pressure systems up to 300 psi (2068 kPa).
Features:
Use with steam, air, noncombustible gases, or other fluids non-corrosive to pressure sensing element.
L404F has snap-acting switching.
Adjustments are made by screws on top of case.
Mount using 1/4 in. NPT female threads or surface mount through base of case.
Product Specifications:
Description: Pressuretrol Controller, Auto recycle, 5 psi to 50 psi.
Application: Provide control of steam, air, non-combustible gases or non-corrosive fluids.
Operating Range (psi): 5 to 50 psi.
Operating Range (kPa): 35 to 350 kPa.
Mounting: 1/4 in. NPT internal thread or surface mount through back of case.
Switch Operation: Auto recycle.
Switching Action: Snap switch makes R-W on pressure rise.
Sensor Element: Stainless Steel diaphragm.
Pipe Connections, Main or High Pressure: 1/4 in. NPT internal thread.
Dimensions (in.): 4 31/32 in. high x 4 1/2 in. wide x 2 3/4 in. deep.
Dimensions (mm): 126 mm high x 114 mm wide x 70 mm deep.
Switch Contact Ratings (120 Vac): 8.0 AFL, 48.0 ALR, 10.0 A resistive.
Switch Contact Ratings (240 Vac): 5.1 AFL, 30.6 ALR, 5.0 A resistive.
Maximum Sustained Operating Pressure (psi): 85 psi.
Maximum Sustained Operating Pressure (kPa): 590 kPa.
Pressure Differential (psi): 6 to 14 psi.
Pressure Differential (kPa): 40 to 100 kPa.
Differential Type: Subtractive.
Temperature Range (F): -35 F to +150 F.
Temperature Range (C): -37 C to +66 C.
Electrical Connections: Screw terminals.
Approvals, Underwriters Laboratories Inc - Listed: File No. MP466, Guide No. MBPR.
Approvals, Canadian Standards Association - Certified: File No. LR95329.
Approvals, Industrial Risk Insurers: Acceptable.
Includes: Ground Screw.
|