2.5%
Design
Outside
summer temperatures and coincident air moisture content that will be exceeded
only 2.5% of the hours from June to September.
In other words, 2.5% design conditions are outdoor temperatures historically
exceeded 73 out of the 2,928 hours in these summer months.
Abatement
Reduction
or removal of a contaminant.
Absolute Humidity
This
is often confused with mixing ratio.
It is the ratio of the mass of water vapor to the unit volume of moist air.
Vaisala products give this output as grams of water per cubic metre of air
(g/m3).
Absolute Pressure
Gauge
pressure plus atmospheric pressure (14.7 lb.per sq.in.) equals absolute
pressure.
Absolute Temperature
Temperature
measured from absolute zero.
Absolute Zero Temperature
Temperature
at which all molecular motion ceases (-460 F. and -273 C.)
Absorbent
Substance
with the ability to take up or absorb another substance.
Absorption Refrigerator
Refrigerator
which creates low temperature by using the cooling effect formed when a
refrigerant is absorbed by chemical substance.
ACCA
A
leading HVAC/R Association - http://www.acca.org/
Acceptable
indoor air quality
Indoor
air that does not contain harmful concentrations of contaminants; air with
which at least 80% of building occupants do not express dissatisfaction.
Accessible Hermetic
Assembly
of a motor and compressor inside a single bolted housing unit.
Accumulator
Storage
tank which receives liquid refrigerant from evaporator and prevents it from
flowing into suction line before vaporizing.
Tank on the suction side of a system that holds excess refrigerant to prevent
slugging the compressor with liquid.
ACGIH
American
Conference of Governmental Industrial Hygienists.
ACH
Air
Changes Per Hour.
The number of times that air in a house is completely replaced with outdoor air
in one hour.
Acid Condition In System
Condition
in which refrigerant or oil in system is mixed with fluids that are acid in
nature.
ACR Tubing
Tubing
used in air conditioning and refrigeration.
Ends are sealed to keep tubing clean and dry.
Action Level
A
term used to identify the level of indoor radon at which remedial action is
recommended.
Action Packet
In
reference to the indoor air quality Tools for Schools Kit.
The packet contains three components - an introductory memo, IAQ Backgrounder,
and IAQ Checklist - to assist school personnel to implement an effective yet
simple indoor air quality program in their school.
Activated Alumina
Chemical
which is a form of aluminum oxide.
It is used as a drier or desiccant.
Activated Carbon
Specially
processed carbon used as a filter drier ; commonly used to clean air.
Actuator
That
portion of a regulating valve which converts mechanical fluid, thermal energy
or electrical energy into mechanical motion to open or close the valve seats.
Add On Heat Pump
Installing
a heat pump in conjunction with an existing fossil fuel furnace.
The result is a dual fuel system.
Adiabatic Compression
Compressing
refrigerant gas without removing or adding heat.
Adjustable Grille
A
grille with linear blades which can be adjusted to vary the direction of the
discharged air.
The linear blades are normally either vertical or horizontal, or both
horizontal and vertical.
Adsorbent
Substance
with the property to hold molecules of fluids without causing a chemical or
physical damage.
Aeration
Act
of combining substance with air.
Aerosol
A suspension
of liquid or solid particles in air.
AFLU (Annual Fuel Utilization Efficiency)
A
rating that reflects the efficiency of a gas furnace in converting fuel to
energy.
A rating of 90 means that approximately 90% of the fuel is utilized to provide
warmth to your home, while the remaining 10% escapes as exhaust.
AFUE (Annual Fuel Utilization Efficiency )
This
number represents how efficiently a furnace converts fuel to energy.
The ratio of annual output of useful energy or heat to the annual energy input
to the furnace.
The higher the AFUE, the more efficient the furnace -- higher efficiency
translates to more savings on fuel bills.
This will range from 80% to 95%.
Percentage of fuel used for heating.
A measure of heating efficiency, in consistent units, determined by applying
the federal test method for furnaces.
This value is intended to represent the ratio of heat transferred to the
conditioned space by the fuel energy supplied over one year.
Agitator
Device
used to cause motion in confined fluid.
AHU (Air Handler Unit)
The
inside part of the A/C system that contains the blower, cooling (evaporator)
coil, and heater.
The part of an HVAC system responsible for moving air, which may also clean,
heat, or cool the air.
This refers to equipment used to provide conditioned air to a space.
The air handler unit generally includes a blower or fan, heating and/or cooling
coils, and related equipment such as controls, condensate drain pans, and air
filters.
Does not include ductwork, registers or grilles, or boilers and chillers.
Air Change
The
amount of air required to completely replace the air in a room or building; not
to be confused with recirculated air.
Air Cleaner
Device
used for removal of airborne impurities.
A device that actively removes impurities from the air, including forced air
filtration systems and electronic air cleaners.
Air cleaners may be added to HVAC systems or stand-alone room units.
Air Cleaning
An
indoor air quality control strategy to remove various airborne particulates
and/or gases from the air.
The three types of air cleaning most commonly used are particulate filtration,
electrostatic precipitation, and gas sorption.
Air Coil
Coil
on some types of heat pumps used either as an evaporator or condenser.
Air Conditioner
Device
used to control temperature, humidity, cleanliness and movement of air in a
confined space.
Air Conditioning
Control
of the temperature, humidity, air movement and cleaning of air in a confined
space.
Air Cooler
Mechanism
designed to lower temperature of air passing through it.
Air Core Solenoid
Solenoid
that has a hollow core instead of a solid core.
Air Diffuser
An
air distribution outlet or grille designed to direct airflow into desired
patterns.
Supply air terminal device, designed to direct airflow into desired patterns,
usually placed in the ceiling, generally of circular, square or rectangular
shape, and composed of divergent deflecting members.
Air Diffusion
Distribution
of the air in a space, called the treated space, by means of devices, called
air terminal devices, in a manner so as to meet certain specified conditions,
such as air change rate, pressure, cleanliness, temperature, humidity, air velocity
and noise level.
Air Distribution
The
transportation of a specified air flow to or from the treated space or spaces,
generally by means of ductwork.
Air Exchange Rate
The
rate of air flow moving through a space, usually expressed in terms of room
volume units per unit of time such as room air changes per hour.
Air Exchange Rate
The
rate at which outside air replaces indoor air in a space.
Expressed in one of two ways: the number of changes of outside air per unit of
time in air changes per hour (ACH); or the rate at which a volume of outside
air enters per unit of time - cubic feet per minute (cfm).
Air Gap
The
space between magnetic poles or between rotating and stationary assemblies in a
motor or generator.
Air Handler
Fan-blower,
filter and housing parts of a system.
Fan-blower, filter, heat transfer coil, and housing parts of a system.
Also known as the blower section and part of the split system, this unit is
commonly in your home or attic and blows the air through your house.
This has to be matched with the condenser properly to assure maximum efficiency.
This will contain your heating and evaporator coil.
Air Infiltration
Leakage
of air into rooms through cracks, windows doors and other openings.
Air Quality Standard
A
government-mandated regulation that specifies the maximum contaminant
concentration beyond which health risks are considered to be unacceptable.
Air Source Equipment
Heat
pumps or air conditioners that uses the outdoor air to transfer heat to and
from the refrigerant in the unit.
Air Terminal Device
A
device located in an opening provided at the boundaries of the treated space to
ensure a predetermined motion of air in this space.
Air Terminal Device, Lighting Troffer
An
air terminal device, usually in the form of a slot or combination of slots,
designed for use with a troffer unit.
Air Terminal Device, Linear
Air
terminal device (grille) with an aspect ratio of 10: 1 or more.
Air Terminal Device, Slot
A
device with one or several slots with an aspect ratio of 10: 1 or more for each
slot (the aspect ratio is the ratio of the length to the width of the closed
rectangular opening).
A slot may or may not have an adjustable member to vary the direction of the
air jet(s) or air flow rate.
Air Terminal Device, Supply
An
air terminal device through which air enters a treated space.
It usually consists of one or several deflecting members which ensure reduction
of the air velocity in the occupied zone as well as efficient mixing of the
supply air with the air in the treated space.
Moreover supply air terminal devices usually determine the direction of the air
jet(s).
Air-Cooled Condenser
Heat
of compression, plus the heat of absorption, is transferred from refrigerant
within coil to surrounding air, either by convection or fan or blower.
Airflow
The
distribution or movement of air.
Ak value (of an air terminal device)
Quotient
obtained by dividing a measured air flow rate by a measured air velocity
according to a specific process and a specific instrument.
Algaecide
Normally
in tablet form, placed in evaporator drain pan.
Used to help slow the growth of bacteria.
Allergens and Pathogens
Biological
material, including bacteria, viruses, fungi, mold spores, pollens, skin flakes
and insect parts are ubiquitous in indoor environments.
These particulates range from less than one to several microns in size.
When airborne, they are usually attached to dust particulates of various sizes
so that all sizes of airborne particulates may include them.
Alternating Current (AC)
Flow
of electricity that constantly changes direction between positive and negative
sides.
Almost all power produced by electric utilities in the United States moves in
current that shifts direction at a rate of 60 times per second.
Ambient
The
surrounding atmosphere; encompassing on all sides; the environment surrounding
a body but undisturbed or unaffected by it.
Ambient Air
The
air surrounding a building; outside air.
Ambient Air Temperature
Surrounding
temperature, such as the outdoor air temperature around a building.
Ampere (A or Amp)
The
primary unit of measurement of electrical current.
One ampere of current is produced in a circuit by 1 volt acting through a
resistance of 1 ohm.
Amplification
An
increase in the numbers or concentration of a microbe or its products through
reproduction and growth of the microbe.
Annual Effects
The
total effects in energy use (measured in megawatthours) and peak load (measured
in kilowatts) caused by all participants in the DSM programs that are in effect
during a given year.
It includes new and existing participants in existing programs (those
implemented in prior years that are in place during the given year) and all
participants in new programs (those implemented during the given year).
The effects of new participants in existing programs and all participants in
new programs should be based on their start-up dates (i.e., if participants
enter a program in July, only the effects from July to December should be
reported).
If start-up dates are unknown and cannot be reasonably estimated, the effects
can be annualized (i.e., assume the participants were initiated into the
program on January 1 of the given year).
The annual effects should consider the useful life of efficiency measures, by
accounting for building demolition, equipment degradation and attrition.
Antimicrobial
Agent
that kills microbial growth.
Appliance Efficiency Standards
California
Code of Regulations, Title 20, Chapter 2, Subchapter 4: Energy Conservation,
Article 4: Appliance Efficiency Standards.
Appliance Efficiency Standards regulate the minimum performance requirements
for appliances sold in California and apply to refrigerators, freezers, room
air conditioners, central air conditioners, gas space heaters, water heaters,
plumbing fittings, fluorescent lamp ballasts and luminaires, and ignition
devices for gas cooking appliances and gas pool heaters.
New National Appliance Standards are in place for some of these appliances and
will become effective for others at a future date.
APR
Air
Purifying Respirator
ARI
(Air-Conditioning and Refrigeration Institute)
Air-Conditioning
and Refrigeration Institute is a nonprofit, voluntary organization comprised of
heating,air conditioning and refrigeration manufacturers.
ARI publishes standards for testing and rating heat pumps and air conditioners
to provide you with a standardized measure of comparison.
So, ARI ensures a level of performance within the industry.
Asbestos
A
class of silicate minerals composed of long, thin fibers.
ASHRAE
A
leading HVAC/R Association - American Society of Heating, Refrigerating and Air
Conditioning Engineers - http://www.ashrae.org/ The trade association that
provides information and sets standards for the industry.
ASTM
American
Society for Testing and Materials.
ASTM
American
Society for Testing and Materials.
Backdrafting
Reverse
flow of combustion gases down the chimney of a vented combustion appliance,
which is often caused by depressurization of the room where the appliance is
located.
A condition where the normal movement of combustion products from a combustion appliance
up a flue is reversed so that the combustion products can enter the building.
Background Concentration
The
level of a contaminant present before the introduction of a new source.
Balance Point
The
lowest outdoor temperature at which the refrigeration cycle of a heat pump will
supply the heating requirements.
Usually a temperatyre between 30°F to 45°F -- at which a heat pump's output
exactly equals the heating needs of the house.
Below the balance point, supplementary electric resistance heat is needed to
maintain indoor comfort.
Balancing
The
process of adjusting the flow of air in duct systems, or water flow in
hot-water heating systems.
Proper balancing is performed using accurate instrumentation to deliver the
right amount of heating or cooling to each area or room of the home.
Bioaerosol
An
airborne microbial contaminant, such as a virus, bacteria, fungus, algae, or
protozoa, or particulate material associated with one of these microorganisms.
Biocide
Substance
or chemicals that kills organisms such as molds.
Biological Contaminants
Agents
derived from, or that are, living organisms (e.g., viruses, bacteria, fungi,
and mammal and bird antigens) that can be inhaled and can cause many types of
health effects including allergic reactions, respiratory disorders,
hypersensitivity diseases, and infectious diseases.
Also referred to as "microbiologicals" or "microbials."
Blower
door
A
large powerful variable-speed fan mounted in a doorway that blows air into
(pressurizes) or sucks air out of (depressurizes) a house.
It's used to test for air leakage in a house.
The size and complexity of the fan varies, but all blower doors have adjustable
frames around the fan so that they can fit snugly into most doorways.
Blower (Fan)
An
air handling device for moving air in a distribution system.
Boiler
A
device for generating steam for power, processing, or heating purposes or for
producing hot water for heating purposes or hot water supply.
Heat from an external combustion source is transmitted to a fluid contained
within the tubes in a boiler shell, a closed vessel in which water is converted
to pressurized steam.
This fluid is delivered to an end-use at a desired pressure, temperature, and
quality.
Boot
A
piece of duct used to connect ducts with registers.
Breathing Zone
The
area of a room in which occupants breathe as they stand, sit, and lie down.
Breathing Zone
That
area of a room in which occupants breathe as they stand, sit, or lie down.
BRI (Building-Related Illness)
Diagnosable
illness whose symptoms can be identified and whose cause can be directly
attributed to airborne building pollutants (e.g., Legionnaire's disease,
hypersensitivity pneumonitis).
Also: A discrete, identifiable disease or illness that can be traced to a
specific pollutant or source within a building.
(Contrast with "Sick building syndrome").
BTU (British Thermal Unit)
The
amount of heat that will raise or lower one pound of water 1 degree F.
at 39.2 degrees F.
One BTU is the equivalent of the heat given off by a single wooden kitchen
match.
The British Thermal Unit is a standard of measure for cooling and heating
capacities.
This is how the capacity of air conditioning is measured.
A standard measure of heat energy in the U.S., commonly used to measure the
energy content of various fuels and steam.
It takes one Btu to raise the temperature of one pound of water by one degree
Fahrenheit at sea level.
For example, it takes about 2,000 Btus to make a pot of coffee.
One Btu is equivalent to 252 calories, 778 foot-pounds, 1055 joules, and 0.293
watt-hours.
Note: In the abbreviation, only the B is capitalized.
For your home, it represents the measure of heat givens off when fuel is burned
for heating or the measure of heat extracted from your home for cooling.
BTUH (British Thermal Unit Per Hour)
Establishes
a time reference to btu input or output rates.
A BTUH is how many BTUs are used per hour.
Buffer zone
An
area within the home between the conditioned zones and the outside.
Thus it normally is not conditioned (for instance, attics, attached garages,
crawlspaces, basements, and enclosed porches).
Building Energy Efficiency Standards
California
Code of Regulations, Title 24, Part 2, Chapter 2-53; regulating the energy
efficiency of buildings constructed in California.
Building, Envelope
the
outer walls, windows, doors, roof, and floors of a building; the building shell.
Building Envelope
Elements
of the building, including all external building materials, windows, and walls,
that enclose the internal space.
Butane
A
hydrocarbon gas found in the earth along with natural gas and oil.
Butane turns into a liquid when put under pressure.
It is sold as bottled gas.
It is used to run heaters, stoves and motors, and to help make petrochemicals.
CAE (Combined Annual Efficiency)
A
measure of the amount of heat produced for every dollar of fuel consumed for
both home heating and water heating.
Calorie
One
energy calorie is equivalent to 4.2 joules.
Thus, it takes 500,000 calories of energy to boil a pot of coffee.
One food calorie equals 1,000 energy calories.
Capacitor
A
device used to start a motor or compressor (or to keep it running after start
up.)
Capacity
(or System Capacity )
The
output or producing ability of a piece of cooling or heating equipment.
Cooling and heating capacity are normally referred to in BTUs.
The capacity of an air conditioner is measured by the amount of cooling it can
do when running continuously.
The total capacity is the sum of the latent capacity (ability to remove
moisture from the air) and sensible capacity (ability to reduce the dry-bulb
temperature).
Each of these capacities is rated in Btus per hour (Btu/h).
The capacity depends on the outside and inside conditions.
As it gets hotter outside (or cooler inside) the capacity drops.
The capacity at a standard set of conditions is often referred to as "tons
of cooling."
Carbon
Dioxide (CO2)
A
colorless, odorless, non-poisonous gas that is a normal part of the air.
Carbon dioxide, also called CO2, is exhaled by humans and animals and is
absorbed by green growing things and by the sea.
A gas which can at high levels (above 1.5 % or 15,000 parts per million), have
physiological effects.
Main indoor source is human respiration; measurements used as indicators of
ventilation conditions.
Carbon Monoxide (CO)
An
colorless, odorless gas that is the product of incomplete fuel combustion or
carbon burns without sufficient air nearby.
It is a chemical asphyxiant; in the bloodstream it effectively prevents the
transport of oxygen to the body's tissues.
CO exposure can affect the lungs, heart, and nervous system, and can cause
death.
Sources include cooling and heating appliances, tobacco smoke, and entrained
exhaust from parking garages and truck idling areas.
A gas, made up of carbon and oxygen molecules, produced by incomplete burning
of carbon or carbonaceous materials, including carbon-based fuels.
including coal, natural gas, gasoline, oil and wood.
It is a major air pollutant on the basis of weight.
Carbon monoxide is also produced from incomplete combustion of many natural and
synthetic products.
For instance, cigarette smoke contains carbon monoxide.
When carbon monoxide gets into the body, the carbon monoxide combines with
chemicals in the blood and prevents the blood from bringing oxygen to cells,
tissues and organs.
The body's parts need oxygen for energy, so high-level exposures to carbon
monoxide can cause serious health effects, with death possible from massive
exposures.
Symptoms of exposure to carbon monoxide can include vision problems, reduced
alertness, and general reduction in mental and physical functions.
Carbon monoxide exposures are especially harmful to people with heart, lung and
circulatory system diseases.
Carboxyhemogoblin Saturation
Carbon
monoxide poisoning.
Carcinogen
An
agent suspected or known to cause cancer.
Ceiling Plenum
The
space between the suspended and structural ceiling used as part of the air
distribution system that accomodates the mechanical and electrical equipment.
This space usually accommodates electrical, communications, and mechanical
connections as well.
The space is kept under negative pressure.
Celsius
A
temperature scale based on the freezing (0 degrees) and boiling (100 degrees)
points of water.
Abbreviated as C in second and subsequent references in text.
Formerly known as Centigrade.
To convert Celsius to Fahrenheit, multiply the number by 9, divide by 5, and
add 32.
For example: 10 degrees Celsius x 9 = 90; 90 / 5 = 12; 18 + 32 = 50 degrees
Fahrenheit.
Central Air Handling Unit (Central AHU)
This
is the same as an Air Handling Unit, but serves more than one area.
Central Forced-Air Heating System
A
piece of equipment that produces heat in a centralized area, then distributes
it throughout the home through a duct system.
CFC (Chlorofluorocarbons or Chlorinated Fluorocarbons)
A
class of refrigerants.
Generally refers to the Chlorofluorocarbon family of refrigerants.
Sometimes called Freon A family of artificially produced chemicals receiving
much attention for their role in stratospheric ozone depletion.
Since they were introduced in the mid-1930s, CFCs have been used as
refrigerants, solvents and in the production of foam material.
These chemicals and some related chemicals have been used in great quantities
in industry, for refrigeration and air conditioning, and in consumer products.
CFCs and their relatives, when released into the air, rise into the
stratosphere, a layer of the atmosphere high above the Earth.
In the stratosphere, CFCs and their relatives take part in chemical reactions
which result in reduction of the stratospheric ozone layer, which protects the
Earth's surface from harmful effects of radiation from the sun.
On a per molecule basis, these chemicals are several thousand times more
effective as greenhouse gases than carbon dioxide.
The 1987 Montreal protocol on CFCs seeks to reduce their production by one-half
by the year 1998.
The 1990 CLEAN AIR ACT includes provisions for reducing releases (emissions)
and eliminating production and use of these ozone-destroying chemicals.
CFM (Cubic Feet per Minute)
A
standard measurement of airflow that indicates how many cubic feet of air pass
by a stationary point in one minute.
The higher the number, the more air is being forced through the system.
A typical system produces 400 CFM per ton of air conditioning.
Charge
Amount
of refrigerant placed in a refrigerating unit.
Chemical Sensitization
Evidence
suggests that some people may develop health problems characterized by effects
such as dizziness, eye and throat irritation, chest tightness, and nasal
congestion that appear whenever they are exposed to certain chemicals.
People may react to even trace amounts of chemicals to which they have become
"sensitized."
Chiller
A
device that produces chilled water to provide air conditioning for large
buildings or cooling for process applications.
A device that cools water, usually to between 40 and 50 degrees Fahrenheit for
eventual use in cooling air.
Circuit
One
complete run of a set of electric conductors from a power source to various
electrical devices (appliances, lights, etc.) and back to the same power source.
Clean Air Act
The
original Clean Air Act was passed in 1963, but the national air pollution
control program is actually based on the 1970 version of the law.
The 1990 Clean Air Act Amendments are the most far-reaching revisions of the
1970 law.
The 1990 amendments are often referred to as as the 1990 Clean Air Act.
Clean Air Act Amendments of 1990
These
ammendments represent a major overhaul of the earlier Clean Air Act of 1970.
Changes include revised provisions for attainment and maintenance of National
Ambient Air Quality Standards, mobile sources, hazardous air pollutants, and
other assorted air quality issues.
In addition, it establishes guidelines for reductions in air pollution.
The Act also specifically limits sulfur dioxide and nitrogen oxide emissions of
power plants.
Cogeneration
Simultaneous
production of two or more forms of useable energy from a single fuel source,
e.g., heat energy and electrical or mechanical power, in the same facility.
Because a typical cogeneration facility uses thermal energy which is generally
vented in a traditional power plant, the process can be 50 to 70 percent more
efficient.
Fuels used in cogeneration facilities may take the form of natural gas,
biomass, oil or coal.
Most cogeneration systems are designed to simultaneously produce electric power
(to be used on site or sold back to an investor-owned utility or both) and
thermal heat for industrial processes or the heating and cooling of buildings.
Cogeneration projects can be any size, from 10 kilowatts to 1,000 megawatts or
more.
Coil
A
cooling or heating element, often including fins, through which treated gas or
liquid is passed, exchanging thermal energy with air surrounding it for heating
or cooling.
Colony Forming Unit (CFU)
A
laboratory measure of fungal concentration, indicating the quantity of viable
organisms collected for a given unit sample.
Comfort Conditioning
The
process of treating air to simultaneously control its temperature, humidity,
cleanliness, and distribution to meet the comfort requirements of the occupants
of the conditioned space.
Comfort Zone
The
range of temperatures, humidities and air velocities at which the greatest
percentage of people feel comfortable.
The range of temperatures over which the majority of persons feel comfortable
(neither too hot nor too cold).
Commercial
The
commercial sector is generally defined as nonmanufacturing business
establishments, including hotels, motels, restaurants, wholesale businesses,
retail stores, and health, social, and educational institutions.
The utility may classify commercial service as all consumers whose demand or
annual use exceeds some specified limit.
The limit may be set by the utility based on the rate schedule of the utility.
Commissioning
The
testing of HVAC systems prior to building occupancy to check whether the
systems meet the operational needs of the building within the capabilities of
the system design.
Start-up of a building that includes testing and adjusting HVAC, electrical,
plumbing, and other systems to assure proper functioning and adherence to
design criteria.
Commissioning also includes the instruction of building representatives in the
use of the building systems.
Compressor
The
heart of an air conditioning or heat pump system.
The large (usually black) part in the condenser (outdoor unit) that pumps
refrigerant.
The pump of a refrigerating mechanism which draws a low pressure on cooling
side of refrigerant cycle and squeezes or compresses the gas into the high
pressure or condensing side of the cycle.
The compressor maintains adequate pressure to cause refrigerant to flow in
sufficient quantities to meet the cooling requirements of the system.
Condenser
This
is the unit that will sit outside and is part of a split system, it contains
the compressor which is the heart of your air conditioner or Heat Pump, it
pumps the refrigerant through your system.
Some people call the condenser the compressor, but the compressor is a
component of the condenser along with the fan motor and condenser coil.
Coil or outdoor coil dissipates heat from the refrigerant, changing the
refrigerant from vapor to liquid.
Condenser Approach Temperature
The
temperature difference between the condenser's refrigerant temperature and the
leaving condenser water temperature.
An ideal indicator of fouling of condenser tubes, which can significantly
degrade chiller efficiency.
Condenser Coil
[Also
see Outdoor Coil] The outdoor portion of a heating or cooling system that
either releases or collects heat from the outside air, depending on the time of
year.
The Condenser Coil is connected directly to the home's Air Handler and is also
known as the Outdoor Coil.
Condensing Unit
Part
of a refrigerating mechanism which pumps vaporized refrigerant from the
evaporator, compresses it, liquefies it in the condenser and returns it to the
refrigerant control.
The outdoor portion of a split system air conditioner contains the compressor
and outdoor coil ignoring the reverse cycle operation, also the outdoor in a
heat pump system.
Conditioned Air
The
air that has been heated, cooled, humidified, or dehumidified to maintain an
interior space within the "comfort zone."
Conditioned
Floor Area
The
floor area of enclosed conditioned spaces on all floors measured from the
interior surfaces of exterior partitions for nonresidential buildings and from
the exterior surfaces of exterior partitions for residential buildings.
Conditioned Space
Enclosed
space that is either directly conditioned space or indirectly conditioned space.
Conditioned Space, Directly
An
enclosed space that is provided with heating equipment that has a capacity
exceeding 10 Btus/(hr-ft2), or with cooling equipment that has a capacity
exceeding 10 Btus/(hr-ft2).
An exception is if the heating and cooling equipment is designed and
thermostatically controlled to maintain a process environment temperature less
than 65 degrees Fahrenheit or greater than 85 degrees Fahrenheit for the whole
space the equipment serves.
Conditioned Space, Indirectly
Enclosed
space that: (1) has a greater area weighted heat transfer coefficient (u-value)
between it and directly conditioned spaces than between it and the outdoors or
unconditioned space; (2) has air transferred from directly conditioned space
moving through it at a rate exceeding three air changes per hour.
Conductance
The
quantity of heat, in Btu's, that will flow through one square foot of material
in one hour, when there is a 1 degree F temperature difference between both
surfaces.
Conductance can be expressed in other units as well.
Conductance values are given for a specific thickness of material, not per inch
thickness.
Conduction
The
transfer of heat through a solid material.
The transfer of heat energy through a material (solid, liquid or gas) by the
motion of adjacent atoms and molecules without gross displacement of the
particles.
Configuration
This
describes the direction in which a furnace outputs heat.
A furnace may have an upflow, downflow or crossflow (horizontal) configuration.
Constant Air Volume Systems
Air
handling system that provides a constant air flow while varying the temperature
to meet heating and cooling needs.
Contactor
In
the condenser, the main switch that turns the condenser on.
Contaminant
An
unwanted constituent that may or may not be associated with adverse health or
comfort effects.
Convection
The
movement of heat by air flow.
Cooling Capacity
The
maximum rate at which cooling equipment removes heat from airflow at operating
conditions.
Cooling Capacity, Latent
Available
refrigerating capacity of an air conditioning unit for removing latent heat
from the space to be conditioned.
Cooling Capacity, Sensible
Available
refrigerating capacity of an air conditioning unit for removing sensible heat
from the space to be conditioned.
Cooling Capacity, Total
Available
refrigerating capacity of an air conditioner for removing sensible heat and
latent heat from the space to be conditioned.
Cooling Degree Day
A
unit of measure that indicates how heavy the air conditioning needs are under
certain weather conditions.
Cooling Load
The
rate at which heat must be extracted from a space in order to maintain the
desired temperature within the space.
Cooling Load Temperature Difference (CLTD)
A
value used in cooling load calculations for the effective temperature
difference (delta T) across a wall or ceiling, which accounts for the effect of
radiant heat as well as the temperature difference.
Cooling System
A
system of air-to-air, liquid-to-air, liquid-to-liquid, etc., heat exchangers,
ducts and/or pipes, etc., for removing head from a system contianing heat
sources, such as power plants, automobile engines, and homes.
Also, an energy Efficiency program promotion aimed at improving the efficiency
of the cooling delivery system, including replacement, in the residential,
commercial, or industrial sectors.
Cooling tower
A
heat transfer device, which cools warm water using outside air.
COP (Coefficient Of Performance)
COP
compares the heating capacity of a heat pump to the amount of electricity
required to operate the heat pump in the heating mode.
COPs vary with the outside temperature: as the temperature falls, the COP falls
also, since the heat pump is less efficient at lower temperatures.
ARI standards compare equipment at two temperatures, 47 F and 17 F, to give you
an idea of the COP in both mild and colder temperatures.
Geothermal equipment is compared at 32 F enter water temperature.
COP & HSPF can not be compared equally.
Air Source Equipment is rated by HSPF or COP and Geothermal equipment is rated
by COP.
Current (Electric)
A
flow of electrons in an electrical conductor.
The strength or rate of movement of the electricity is measured, e.g., in
amperes.
Damper
A
device that is located in ductwork to adjust air flow.
This movable plate opens and closes to control airflow.
Dampers are used effectively in zoning to regulate airflow to certain rooms.
There are basically two types of dampers: Manual and motorized.
A manual damper generally consists of a sheet metal (or similar material) flap,
shaped to fit the inside of a round or rectangular duct.
By rotating a handle located outside of the duct a technician can adjust (see
Balancing) air flow to match the needs of a particular area or room.
A motorized damper is generally used in a zoned system (see Zoning) to
automatically deliver conditioned air to specific rooms or zones.
In particular, the following types, can be distinguished:
Multiple leaf
dampers, comprising of a number of blades (or shutters) of opposed or parallel
leaf type.
Single leaf dampers (the flap being mounted at one end), commonly called
splitter dampers.
Hit-and-miss dampers, having two or more slotted slide mechanism.
Butterfly dampers, with two flaps in "V" arrangement.
Dampers
Controls
that vary airflow through an air outlet, inlet, or duct.
A damper position may be immovable, manually adjustable or part of an automated
control system.
db (Decibel)
A
decibel describes the relative loudness of a sound.
Some common sounds are fairly close to a typical air conditioner or heat pump's
sound level: human voice, 7.0 decibels; blender, 8.8 decibels.
DDC (Direct Digital Control)
Direct
Digital Control
Defrost
Cycle
The
process of removing ice or frost buildup from the outdoor coil during the
heating season.
Degree Day
A
unit, based upon temperature difference and time, used in estimating fuel
consumption and specifying nominal annual heating load of a building.
When the mean temperature is less than 65 degrees Fahrenheit the heating degree
days are equal to the total number of hours that temperature is less than 65
degrees Fahrenheit for an entire year.
Dehumidification
The
reduction of water vapor in air by cooling the air below the dew point; removal
of water vapor from air by chemical means, refrigeration, etc.
Delta (or Delta T)
A
difference in temperature.
Often used in the context of the difference between the design indoor
temperature and the outdoor temperature.
Demand Billing
The
electric capacity requirement for which a large user pays.
It may be based on the customer's peak demand during the contract year, on a
previous maximum or on an agreed minimum.
Measured in kilowatts.
Demand Charge
The
sum to be paid by a large electricity consumer for its peak usage level.
Demand (Utility)
The
rate at which electricity or natural gas is delivered to or by a system,, part
of a system, or piece of equipment, e.g., to end users, at a given instant or
averaged over any designated period of time.
Electricity demand is typically expressed in kilowatts.
Design Conditions
Cooling
loads vary with inside and outside conditions.
A set of conditions specific to the local climate are necessary to calculate
the expected cooling load for a home.
Inside conditions of 75 degrees Fahrenheit and 50% relative humidity are
usually recommended as a guideline.
Outside conditions are selected for the 2.5% design point.
Dewpoint
Is
the temperature at which air becomes saturated with water and begins to
condense - forming a dew.
Therefore at 100 % RH the ambient or process temperature equals the dewpoint
temperature.
The more negative the dewpoint temperature is from the ambient temperature the
less the risk of condensation and the drier the gas or air stream.
Diffusers and Grilles
Components
of the ventilation system that distribute and return air to promote air
circulation in the occupied space.
Generally speaking, supply air enters a space through a diffuser or vent and return
air leaves a space through a grille.
Dilution
A
mitigation strategy that lowers the concentration of airborne contaminants by
increasing the fraction of outdoor air in the supply airstream.
Direct Current (DC)
Electricity
that flows continuously in the same direction.
Direct Expansion (Refrigeration)
Any
system that, in operation between an environment where heat is absorbed (heat
source), and an environment into which unwanted heat is directed (heat sink) at
two different temperatures, is able to absorb heat from the heat source at the
lower temperature and reject heat to the heat sink at the higher temperature.
The cooling effect is obtained directly from a fluid called a refrigerant that
absorbs heat at a low temperature and pressure, and transfers heat at a higher
temperature and higher pressure.
Direct Gas-Fired Heater
The
burner fires directly in the air stream being heated, rather than through a
heat exchanger.
100% of available BTUs are delivered to the heated space because no flue or
heat exchanger is required.
This results in no wasted energy.
DOE (Department of Energy)
The
Department of Energy is a federal agency in charge of setting industry
efficiency standards and monitoring the consumption of energy sources.
Double Glazing
Windows
having two sheets of glass with an airspace between.
Downflow
A
type of furnace that takes cool air from the top and blows warm air to the
bottom - common where your furnace must be located in a second-floor closet or
utility area.
Downflow Furnace
A
furnace that pulls in cool return air from the top and blows/expels warm air at
the bottom - common where your furnace must be located in a second-floor closet
or utility area.
Drain Trap
A
dip in the drain pipe of sinks, toilets, floor drains, etc., which is designed
to stay filled with water, thereby preventing sewer gases from escaping into
the room.
Drier
Sometimes
called filter/drier, it removes moisture and keeps the refrigerant clean.
Dry Bulb Temperature (DB)
The
temperature measured by a standard thermometer.
A measure of the sensible temperature of air.
Dual Fuel System
A
dual heating system, for example a heat pump and a fossil fuel furnace.
Dual-Duct System
A
central plant heating , ventilation and air conditioning (HVAC ) system that
produces conditioned air at two temperatures and humidity levels.
The air is then supplied through two independent duct systems to the points of
usage where mixing occurs.
Dual-Paned (Double-glazed)
Two
panes of glass or other transparent material, separated by a space.
Duct
A
pipe or closed conduit made of sheet metal, fiberglass board, or other suitable
material used for conducting air to and from an air handling unit.
A passageway made of sheet metal or other suitable material used for conveying
air or other gas at relatively low pressures.
Duct tape
This
(initially) sticky tape is unfortunately the most common material used to seal
duct connections.
Care must be taken when it's applied.
For effective sealing, the surface it is applied to must be clean--free of
dust, dirt, oil, or other substances.
Duct tape has a tendency to lose adhesion with age, especially when used on
ducts in unconditioned spaces.
Ductwork
A
pipe or closed conduit made of sheet metal, fiberglass board, or other suitable
material used for conducting air to and from an air handling unit.
Hollow pipes or channels that carry/transfer air from the Air Handler to the
air vents throughout your home.
The delivery system through which warm air from the furnace is brought to where
it's needed.
Ductwork is made of sheet metal, fiberglass, or flexible plastic, and can be
round or rectangular in shape.
Ductwork is one of the most important components of a home heating and cooling
system.
Dust
Dust
is comprised of particles in the air that settle on surfaces.
Large particles settle quickly and can be trapped by the body's defense
mechanisms.
Small particles are more likely to be airborne and are capable of passing
through the body's defenses and entering the lungs.
Economizer, Air
A
ducting arrangement and automatic control system that allows a heating,
ventilation and air conditioning (HVAC) system to supply up to 100 percent outside
air to satisfy cooling demands, even if additional mechanical cooling is
required.
Economizer, Water
A
system which uses either direct evaporative cooling, or a secondary
evaporatively cooled water loop and cooling coil to satisfy cooling loads, even
if additional mechanical cooling is required.
EER - (Energy Efficiency Ratio)
A
ratio calculated by dividing the cooling capacity in Btu's per hour (Btuh) by
the power input in watts at any given set of rating conditions, expressed in
Btuh per watt (Btuh/watt).
EER & SEER can not be compared equally.
Air source equipment is rated by SEER and geothermal equipment is rated by EER.
EER changes with the inside and outside conditions, falling as the temperature
difference between inside and outside gets larger.
Effective area (of an air terminal device)
The
smallest net area of an air terminal device used by the air stream in passing
through the air terminal device.
Efficiency
A
rating on comfort equipment is similar to the miles per gallon rating on your
car.
The higher the rating number, the more efficient the system and the lower your
fuel consumption will be.
You can save a lot of money with a high efficiency unit.
Depending on your local climate, lifestyle and electricity rates, savings will
vary.
For furnaces.
it is the rate at which a furnace maximizes fuel use.
This rate is numerically described as a ratio called AFUE (see AFUE).
As of January, 1991, no furnaces can be manufactured with efficiencies lower
than 78% afue.
High efficiency furnaces will be rated 85 to 95% afue.
Electric Radiant Heating
A
heating system in which electric resistance is used to produce heat which
radiates to nearby surfaces.
There is no fan component to a radiant heating system.
Electric Rate Schedule
A
statement of the electric rate and the terms and conditions governing its
application, including attendant contract terms and conditions that have been
accepted by a regulatory body with appropriate oversight authority.
Electric Resistance Heater
A
device that produces heat through electric resistance.
For example, an electric current is run through a wire coil with a relatively
high electric resistance, thereby converting the electric energy into heat
which can be transferred to the space by fans.
Electrostatic air cleaner
A
device that uses an electrical charge to trap particles traveling in the air
stream.
Emergency Heat (Supplementary Electric Heat)
The
back up electric heat built into a heat pump system.
The same as an auxiliary heater, except it is used exclusively as the heat
source when the heat pump needs repair.
Emission Standard
A
voluntary guideline or government regulation that specifies the maximum rate at
which a contaminant can be released from a source.
Encapsulate
A
mitigation technique that reduces or eliminates emissions from a source by
sealing with an impenetrable barrier.
Endotoxin
A
biological agent that is part of the outer membrane of some bacteria.
Endotoxins are highly toxic, capable of causing fever, malaise, respiratory
distress, even death.
Energy
Broadly
defined, is the capability of doing work.
More specifically, it is the capacity for doing work as measured by the
capability of doing work (potential energy) or the conversion of this
capability to motion (kinetic energy).
Forms of energy include: thermal, mechanical, electrical and chemical.
Energy may be transformed from one form into another form useful for work.
Most of the world¹s convertible energy comes from fossil fuels that are burned
to produce heat that is then used as a transfer medium to mechanical or other
means in order to accomplish tasks.
Electrical energy is usually measured in kilowatt-hours, while heat energy may
be measured in British thermal units or other traditional non-metric
speciallized units in addition to metric units.
In the electric power industry, energy is more narrowly defined as electricity
supplied over time, expressed in kilowatts.
Energy Efficiency
Refers
to programs that are aimed at reducing the energy used by specific end-use
devices and systems, typically without affecting the services provided.
These programs reduce overall electricity consumption (reported in
megawatthours), often without explicit consideration for the timing of
program-induced savings.
Such savings are generally achieved by substituting technically more advanced
equipment to produce the same level of end-use services (e.g.
lighting, heating, motor drive) with less electricity.
Examples include high-efficiency appliances, efficient lighting programs,
high-efficiency heating, ventilating and air conditioning (HVAC) systems or
control modifications, efficient building design, advanced electric motor
drives, and heat recovery systems.
Energy Management System
A
control system (often computerized) designed to regulate the energy consumption
of a building by controlling the operation of energy consuming systems, such as
the heating, ventilation and air conditioning (HVAC), lighting and water
heating systems.
Enforcement
The
legal methods used to make polluters obey the CLEAN AIR ACT.
Enforcement methods include citations of polluters for violations of the law
(citations are much like traffic tickets), fines and even jail terms.
EPA and the state and local governments are responsible for enforcement of the
Clean Air Act, but if they don't enforce the law, members of the public can sue
EPA or the states to get action.
Citizens can also sue violating sources, apart from any action EPA or state or
local governments have taken.
Before the 1990 Clean Air Act, all enforcement actions had to be handled
through the courts.
The 1990 Clean Air Act gave EPA authority so that, in some cases, EPA can fine
violators without going to court first.
The purpose of this new authority is to speed up violating sources' compliance
with the law and reduce court time and cost.
Enthalpy
The
quantity of heat necessary to raise the temperature of a substance from one
point to a higher temperature.
The quantity of heat includes both latent and sensible.
Envelope
The
geometrical surface of the points of an air jet, corresponding to a determined
value of the measured air velocity.
This velocity is generally called «terminal velocity».
Also, the air barrier that separates the conditioned space from the outside and
from unconditioned spaces like attics and garages.
Environmental Agents
Conditions
other than indoor air contaminants that cause stress, comfort, and/or health
problems (e.g., humidity extremes, drafts, lack of air circulation, noise, and
over-crowding).
Environmental Tobacco Smoke (ETS)
The
combination of sidestream and mainstream smoke that is emitted from a burning
cigarette; also called second-hand smoke.
Environmental Tobacco Smoke (ETS)
Mixture
of smoke from the burning end of a cigarette, pipe, or cigar and smoke exhaled
by the smoker.
EPA (Environmental Protection Agency)
Environmental
Protection Agency - http://www.epa.gov/ A federal agency created in 1970 to
permit coordinated governmental action for protection of the environment by
systematic abatement and control of pollution through integration of research,
monitoring, standards setting and enforcement activities.
EPA administers federal environmental policies, enforces environmental laws and
regulations, performs research, and provides information on environmental
subjects.
The agency also acts as chief advisor to the President on U.S. environmental
policy and issues.
Epidemiological
Dealing
with the scientific study of the incidence, control, and spread of disease in a
population.
Ergonomics
The
science that investigates the impact of people's physical environment on their
health and comfort (e.g., chair design, monitor location, desk configuration or
height, etc.)
ERV
(Energy Recovery Ventilator)
This
device preheats incoming outside air during the winter and pre-cools incoming
air during the summer to reduce the impact of heating and or cooling the indoor
air.
This means that smaller capacity heating and cooling systems can be used in
homes, which results in lower installation costs, lower peak demand for energy,
and lower operating costs.
Evaporative Cooler
A
type of cooling equipment that turns air into moist, cool air by saturating the
air with water vapor.
It does not cool air by use of a refrigeration unit.
This type of equipment is commonly used in warm, dry climates.
Evaporative Cooling
Cooling
by exchange of latent heat from water sprays, jets of water, or wetted material.
Evaporator Approach Temperature
The
temperature difference between the evaporator¹s refrigerant temperature and the
leaving chilled water temperature.
Evaporator Coil
[Also
see Indoor Coil] The evaporator coil is located inside your house in a split
system in the airhandler, or above the gas furnace.
This will produce cooling in the air conditioning mode and heating in a Heat
Pump mode.
This coil section in the evaporator is where refrigerant evaporates and absorbs
heat from air passed over the coil.This is also very important in removing
humidity from your home.
Exfiltration
Uncontrolled
air leakage out of a building.
Exfiltration
Air
flow outward through a wall, building envelope, etc.
Exhaust
Air
removed deliberately from a space, by a fan or other means, usually to remove
contaminants from a location near their source.
The air flow leaving the treated space.
Exhaust may be accomplished by one or more of the following methods:
a. Extraction: exhaust in
such a manner that the air is discharged into the atmosphere.
b. Relief: exhaust in such a manner that the air is allowed to escape
from the treated space if the pressure in that space rises above a specified
level.
c. Recirculation: exhaust in which the air is returned to the air
treatment system.
d. Transfer: exhaust in which air passes from the treated space to
another treated space.
Exhaust
Air Flow Rate
Volume
of air leaving an exhaust air terminal device within a time unit.
Exhaust Air Terminal Device
Air
terminaI device through which air leaves the treated space.
Exhaust Ventilation
Mechanical
removal of air from a portion of a building (e.g., piece of equipment, room, or
general area).
Fahrenheit (F)
A
temperature scale in which the boiling point of water is 212 degrees and its
freezing point is 32 degrees.
To convert Fahrenheit to Celsius, subtract 32, multiply by 5, and divide the
product by 9.
For example: 100 degrees Fahrenheit - 32 = 68; 68 x 5 = 340; 340 / 9 = 37.77
degrees Celsius.
Fan Coil
An
indoor component of a heat pump system used in place of a furnace, to provide
additional heating on cold days when the heat pump does not provide adequate
heating.
A component of a heating, ventilation and air conditioning (HVAC) system
containing a fan and heating or cooling coil, used to distribute heated or
cooled air.
FAQ (Frequently Asked Questions)
Used
to mean a list of frequently asked questions.
Filter
A
device for removing dust particles from air or unwanted elements from liquids.
Fire Valves (or Fire Dampers)
Components
which are installed in an air distribution system between two fire separating
compartments and are designed to prevent propagation of fire and/or smoke.
Generally are kept open by mechanical restraint, whose effect is canceled under
specific conditions.
The valve is then closed automatically.
Flame roll-out
A
dangerous situation that occurs when flame is pushed out of the bottom of a
combustion appliance.
It can lead to fires.
Flex duct
Usually
installed in a single, continuous piece between the register and plenum box, a
flexible duct usually has an inner lining and an insulated coating on the
outside.
Flow Hood
A
diagnostic tool used to measure air flow through ducts, supply registers, and
return grilles.
Device that easily measures airflow quantity, typically up to 2,500 cfm.
Follow-Up Testing
The
testing designed to confirm the results of the initial testing using identical
testing devices and similar test conditions.
Forced Air
This
describes a type of heating system that uses a blower motor to move air through
the furnace and into the ductwork.
Heating and or cooling system that connects to the conditioned space with
duct-work that uses air as the moving fluid.
The heating or cooling can come from any number of sources.
Forced Air Unit (FAU)
A
central furnace equipped with a fan or blower that provides the primary means
for circulation of air.
Formaldehyde
Formaldehyde
is a colorless water-soluble gas.
Due to its wide use, it is frequently considered separately from other volatile
organic compounds (VOCs) Frequency
The
number of cycles which an alternating current moves through in each second.
Standard electric utility frequency in the United States is 60 cycles per
second, or 60 Hertz.
Fungi
A
large group of organisms including molds, mildews, yeasts, mushrooms, rusts,
and smuts.
Any of a group of parasitic lower plants that lack chlorophyll.
Most fungi produce spores, which are broadcast through the air so that
virtually all environmental surfaces will have some fungal material.
Most health effects are associated with allergic responses to antigenic
material or toxic effects from mycotoxins.
Fungi also generate certain volatile organic compounds.
Fungicide
Substance
or chemical that kills fungi.
Furnace
That
part of an environmental system which converts gas, oil, electricity or other
fuel into heat for distribution within a structure.
Furnace, Horizontal
A
furnace that lies on its side, pulling in return air from one side and
expelling warm air from the other.
Gas Sorption
Devices
used to reduce levels of airborne gaseous compounds by passing the air through
materials that extract the gases.
Geothermal Energy
Natural
heat from within the earth, captured for production of electric power, space
heating or industrial steam.
Geothermal Equipment
Heat
pumps that uses the ground to transfer heat to and from the refrigerant in the
unit.
The unit circulates water through a heat exchanger in the to a closed loop
buried in the ground or by pumping water from a well through the unit.
Geothermal Gradient
The
change in the earth's temperature with depth.
As one goes deeper, the earth becomes hotter.
Global Climate Change
Gradual
changing of global climates due to buildup of carbon dioxide and other
greenhouse gases in the earth's atmosphere.
Carbon dioxide produced by burning fossil fuels has reached levels greater than
what can be absorbed by green plants and the seas.
Greenhouse Effect
The
presence of trace atmospheric gases make the earth warmer than would direct
sunlight alone.
These gases (carbon dioxide [CO2], methane [CH4], nitrous oxide [N2O],
tropospheric ozone [O3], water vapor [H2O], and chlorofluorocarbons) allow
visible light and ultraviolet light (shortwave radiation) to pass through the
atmosphere and heat the earth's surface.
This heat is re-radiated from the earth in form of infrared energy (longwave
radiation).
The greenhouse gases absorb part of that energy before it escapes into space.
Thus the greenhouse effect allows solar radiation to penetrate but absorbs the
infrared radiation returning to space.
This process of trapping the longwave radiation specifically is known as the
greenhouse effect.
Scientists estimate that without the greenhouse effect, the earth's surface
would be roughly 54 degrees Fahrenheit colder than it is today -- too cold to
support life as we know it.
See GLOBAL CLIMATE CHANGE.
Greenhouse Effect (Relating to Buildings)
The
characteristic tendency of some transparent materials (such as glass) to
transmit radiation with relatively short wavelengths (such as sunlight) and
block radiation of longer wavelengths (such as heat).
This tendency leads to a heat build-up within the space enclosed by such a
material.
Grille
An
air terminal device with multiple passages for the air.
Grilles
Coverings
for the ducts where they open to the conditioned space.
(Same as Registers)
Half-Life
The
amount of time it takes for half of the existing amount of a radioactive
element to decay to non-radioactive products.
HCFC (Hydrochlorofluorocarbon)
A
class of refrigerants.
Generally refers to Halogenated Chlorofluorocarbon family of refrigerants.
Heat Balance
The
outdoor temperature at which a building's internal heat gain (from people,
lights and machines) is equal to the heat loss through windows, roof and walls.
Heat Capacity
The
amount of heat necessary to raise the temperature of a given mass one degree.
Heat capacity may be calculated by multiplying the mass by the specific heat.
Heat Engine
An
engine that converts heat to mechanical energy.
Heat Exchanger
This
is a device that enables furnaces to transfer heat from combustion safely into
breathable air.
The primary heat exchanger transfers heat from combustion gases to the air
blowing through the ductwork.
It's vital that none of the combustion gas itself gets into the airstream.
The primary heat exchanger handles the hottest gases.
This device transfers heat from outgoing stale air to incoming cold air.
In warm climates, this process can be reversed.
In high efficiency furnaces, secondary heat exchangers recover heat that used
to be vented up the chimney with the exhaust gases.
By recovering this heat, the furnace becomes more efficient.
Part of the heat recovered here causes the water and acid to condense out of
the exhaust gas.
Because this liquid is corrosive, secondary heat exchangers must be designed to
prevent deterioration.
Usually this means they are made of stainless steel or some derivative of it.
Heat Gain
The
amount of heat gained, measured in BTU's, from a space to be conditioned, at
the local summer outdoor design temperature and a specified indoor design
condition.
An increase in the amount of heat contained in a space, resulting from direct
solar radiation, heat flow through walls, windows, and other building surfaces,
and the heat given off by people, lights, equipment, and other sources.
Heat Loss
The
amount of heat lost, measured in BTU's from a space to be conditioned, at the
local winter outdoor design temperature and a specified indoor design condition.
A decrease in the amount of heat contained in a space, resulting from heat flow
through walls, windows, roof and other building surfaces and from exfiltration
of warm air.
Heat Pump
A
heating and air conditioning unit that heats or cools by moving heat.
A Heat Pump is a reverse cycle air conditioner.
The Heat Pump uses a compression cycle system to supply heat or remove heat
remove a temperature controlled space.
An air-conditioning unit which is capable of heating by refrigeration,
transferring heat from one (often cooler) medium to another (often warmer)
medium, and which may or may not include a capability for cooling.
This reverse-cycle air conditioner usually provides cooling in summer and
heating in winter.
When you run your air conditioner, your outdoor unit will be blowing hot air,
(in other words, removing the heat from your home and sending it outside).
When you run your heat pump, you reverse the flow of refrigerant and remove the
heat from the atmosphere outside and blow it inside.
When the temperature dips below 40 degrees outside, the Heat Pump labors in
producing heat so they install a back up or auxiliary electric heat strip to
supplement the Heat Pump.
Electric Heat strips are very expensive to operate.
In southern climates where it rarely dips below 40 degrees the heat pump is
very efficient.
A 3 to 1 savings in heating compared to electric heat strips.
Heat Pump Cooling Mode
In
the cooling cycle of a Heat Pump , you are removing hot air from inside the
house and sending it outside.
You can feel the hot air outside, over the condenser fan motor.
Heat Pump Heating Mode
In
the heating mode of a Heat Pump the refrigerant cycle is reversed and you are
now removing the heat from the outside and sending it inside the house.
You can feel the cool air outside, over the condenser fan motor.
When temperatures go below 40 degrees Heat Pumps labor in producing heat and
must use back up electric heat strips.
Heat strips cost 3 times as much to operate as a Heat Pump when producing heat.
Heat Rate
A
number that tells how efficient a fuel-burning power plant is.
The heat rate equals the Btu content of the fuel input divided by the
kilowatt-hours of power output.
Heat Source
A
body of air or liquid from which heat is collected.
In an air source heat pump, the air outside the house is used as the heat
source during the heating cycle.
Heat Transfer
Flow
of heat energy induced by a temperature difference.
Heat flow through a building envelope typically flows from a heated, or hot
area to a cooled, or cold area.
Heating Degree Day
A
unit that measure the space heating needs during a given period of time.
Heating Load
The
rate at which heat must be added to a space in order to maintain the desired
temperature within the space.
Heating System
Energy
Efficiency program promotion aimed at improving the efficiency of the heating
delivery system, including replacement, in the residential, commercial, or
industrial sectors.
Hertz
A
unit of electromagnetic wave frequency that is equal to one cycle per second.
-- It is named after Henrich R.
Hertz.
HFC (Hydrofluorocarbon)
A
class of refrigerants.
Generally refers to Hydrofluorocarbon family of refrigerants
High-Efficiency
Particulate Air (HEPA) Filter
A
specialized filter capable of removing 99.97% of particulates 0.3 µ in diameter.
High efficiency particulate arrestance (filters).
Home Energy Assistance Program (HEAP)
A
centrally operated direct payment program that assists eligible households in
offsetting the cost of heating and cooling their homes.
Payments are generally made in the form of dual party warrants (checks) made
payable to the applicant and their designated utility company.
For example, the program is administered in California by the California
Department of Economic Opportunity using federal and state funds.
Horsepower (HP)
A
unit for measuring the rate of doing work.
One horsepower equals about three-fourths of a kilowatt (745.7 watts).
House Dust Mite
A
common microscopic household arachnid, which feeds on shed skin scales, and so
tends to concentrate around mattresses and furniture.
Antigens present in the mite's excreta are implicated in cases of allergic
asthma and allergic rhinitis.
HRV (Heat Recovery Ventilator)
This
device bring fresh, outside air into a home while simultaneously exhausting
stale indoor air outside.
In the process of doing this, an HRV removes heat from the exhaust air and
transfer it to the incoming air, pre-heating it.
This allows for the reclamation of much of the energy that otherwise would
simply be vented outside.
The end result: home comfort systems operate more efficiently.
HSPF (Heating Seasonal Performance Factor)
Indicates
how efficiently a Heat Pump is working.
A higher number means the unit works more efficiently.
Heating Seasonal Performance Factor is similar to SEER, but it measures the
efficiency of the heating portion of your heat pump.
Like SEER, industry minimums have been raised recently, and the minimum is now
6.80 HSPF.
Most new units have ratings from 7.0 to 9.4.
A representation of the total heating output of a central air-conditioning heat
pump in Btus during its normal usage period for heating, divided byu the total
electrical energy input in watt-hours during the same period, as determined
using the specified test procedures.
Efficiency is derived according to federal test methods by using the total Btus
during its normal usage period for heating divided by the total electrical
energy input in watt-hours during the same period.
The total heating output of a heat pump during its normal annual usage period
for heating divided by the total electric power input in watt-hours during the
same period.
COP & HSPF can not be compared equally.
Air Source equipment is rated by HSPF or COP and Geothermal equipment is rated
by COP.
ARI standards compares air source equipment at two temperatures, 47 F and 17 F.
Geothermal equipment is compared at 32 F enter water temperature.
Humidifier
A
device that adds moisture to warm air being circulated or directed into a space.
This adds necessary moisture to protect your furnishings and reduce static
electricity.
Humidistat
A
device designed to regulate humidity input by reacting to changes in the
moisture content of the air.
Much like a thermostat but turns the system on & off by sensing the
humidity level.
Humidity
The
amount of moisture in the air.
Air conditioners remove moisture for added comfort.
HVAC (Heating, Ventilating and Air Conditioning)
Heating,
Ventilating and Air Conditioning
HVAC/R
(Heating, Ventilating, Air Conditioning, & Refrigeration)
Heating,
Ventilating, Air Conditioning, & Refrigeration
Hydronic
Heating
A
system that heats a space using hot water which may be circulated through a
convection or fan coil system or through a radiant baseboard or floor system.
IAQ Backgrounder
A
component of the IAQ Tools for Schools Action Packet that provides a general
introduction to IAQ issues in educational facilities.
IAQ Coordinator
An
individual (usually with facility management) who provides leadership and
coordination of all IAQ activities.
IAQ (Indoor Air Quality)
Indoor Air
Quality - characteristics of the indoor climate of a building, including
the gaseous composition, temperature, relative humidity, and airborne
contaminant levels.
IAQ Management Plan
A
set of flexible and specific steps for preventing and resolving IAQ problems in
any kind of commercial facility.
Indicator Compounds
Chemical
compounds, such as carbon dioxide, whose presence at certain concentrations may
be used to estimate certain building conditions (e.g., airflow, presence of
sources).
Indoor Air Pollutant
Particles
and dust, fibers, mists, bioaerosols, and gases or vapors.
Indoor Coils
[Also
see Evaporator Coil] Refrigerant containing portion of a fan coil unit similar
to a car radiator, typically made of several rows of copper tubing with
aluminum fins.
A homes comfort system consist of two components: the outdoor unit (air
conditioner or heat pump) and the indoor unit (coil or blower coil).
Combinations of various units will result in vastly different efficiency
ratings.
Unreasonably high efficiency ratings can be created by using unrealistic indoor
and out door equipment combinations.
The term "most popular coil" indicates the actual tested
combinations; other ratings may be simulated and unrealistic.
Be sure that the efficiency ratings you are comparing are for "most
popular coil." You'll know the ratings are attainable and close to reality.
Indoor Unit
This
is usually located inside the house and contains the indoor coil, fan, motor,
and filtering device, sometimes called the air handler.
Induction
Process
by which the primary air sets into motion an air volume, called secondary air,
in the room.
Induction ratio (i)
Ratio
of the total air flow rate to the primary air flow rate.
Industrial
The
industrial sector is generally defined as manufacturing, construction, mining,
agriculture, fishing, and forestry establishments (Standard Industrial
Classification [SIC] codes 01-39).
The utility may classify industrial service using the SIC codes, or based on
demand or annual usage exceeding some specified limit.
The limit may be set by the utility based on the rate schedule of the utility.
Infiltration
Air
movement into an enclosed space through cracks and openings.
Unintentional movement of outdoor air into a house.
Air flow inward into a space through walls, leaks around doors and windows or
through the building materials used in the structure.
It results from the forces of wind, temperature difference, and HVAC operation.
ISO 9000
A
family of international standards for quality management and assurance by the
ISO (International Standards Organization).
IWC (Inches of water column)
Commonly
used in the USA
Joule
A
unit of work or energy.
It takes ~ 1,000 joules to equal a British thermal unit.
It typically takes ~ 1 million joules to make a pot of coffee.
KBTU (kBtu)
One-thousand
(1,000) Btus.
Kilovolt (kv)
One-thousand
volts (1,000).
Distribution lines in residential areas usually are 12 kv (12,000 volts).
kW (kilowatt or kW)
A
kilowatt equals one thousand (1,000) watts.
A unit of measure of the amount of electric power production needed to operate
given equipment.
On a hot summer afternoon a typical home, with central air conditioning and
other equipment in use, might have a demand of four kW.
An electric power capacity of one kW is sufficient to power ten 100-watt light
bulbs.
kWh (kilowatt hour or kWh)
A
kilowatt hour (kWh) is the amount of kilowatts of electricity used in one hour
of operation of any equipment.
The most commonly-used unit of measure telling the amount of electricity
consumed over time.
It means one kilowatt of electricity supplied for one hour.
In 1989, a typical California household consumes 534 kWh in an average month.
A typical electric consumer in Pennsylvania currently uses 500 kWh per month of
electricity.)
Latent
Cooling Load (or Latent Load)
The
cooling load caused by moisture in the air.
The net amount of moisture added to the inside air by plants, people, cooking,
infiltration, and any other moisture source.
The amount of moisture in the air can be calculated from a combination of
dry-bulb and wet-bulb temperature measurements.
Latent Heat
Heat,
that when added or removed, causes a change in state - but no change in
temperature.
A change in the heat content that occurs without a corresponding change in
temperature, usually accompanied by a change of state (as from liquid to vapor
during evaporation).
Life Extension
A
term used to describe capital expenses which reduce operating and maintenance
costs associated with continued operation of electric utility boilers and other
equipment.
Such boilers usually have a 40 year operating life under normal circumstances.
Life-Cycle Cost
Amount
of money necessary to own, operate and maintain a building, system, plant,
piece of equipment, etc., over its useful life.
Load
The
amount of electric power supplied to meet one or more end user's needs.
The amount of electric power delivered or required at any specific point or
points on a system.
The requirement originates at the energy consuming equipment of the consumers.
Load Building
Refers
to programs that are aimed at increasing the usage of existing electric
equipment or the addition of electric equipment.
Examples include industrial technologies such as induction heating and melting,
direct arc furnaces and infrared drying; cooking for commercial establishments;
and heat pumps for residences.
Load building should include programs that promote electric fuel substitution.
Load building effects should be reported as a negative number, shown with a
minus sign.
Load Estimate
A
series of studies performed to determine the heating or cooling requirements of
your home.
An energy load analysis uses information such as the square footage of your
home, window and door areas, insulation quality and local climate to determine
the heating and cooling capacity needed by your furnace, heat pump or air
conditioner.
When referring to heating, this is often known as a Heat Loss Analysis, since a
home's heating requirements are determined by the amount of heat lost through
the roof, entry ways and walls.
Local Exhaust Ventilation
An
industrial ventilation system that captures and removes contaminants emitted
from nearby sources before dilution into ambient workplace air can occur.
Make-Up Air
See
"Outdoor Air Supply."
Man-Made
Mineral Fibers (MMMF)
Fiber
insulation products including glass wool, fiberglass, rock wool, slag wools, as
well as refractory ceramic fibers, which are used for fireproofing.
Manometer
An
instrument that measures air pressure differences between locations.
Tubes are usually attached to a manometer and run to the spaces where pressures
are measured.
Manual D
Manual
D is the ACCA method for designing duct systems.
Contractors often find it a laborious process and most duct systems are just
installed, not designed.
The amount of time necessary to design a duct system is certainly warranted in
tract construction where the design is used repeatedly and for custom homes
where the total cost of the home warrants a proper design.
In short, designing a duct system is essential for proper equipment performance
and customer comfort.
Manual J
Manual
J is a widely accepted method of calculating the sensible and latent cooling
(and heating) loads under design conditions.
It was jointly developed by the Air Conditioning Contractors of America (ACCA)
and the Air-Conditioning and Refrigeration Institute (ARI).
Manual S
Manual
S is the ACCA method of selecting air conditioning equipment to meet the design
loads.
It ensures that both the sensible capacity and the latent capacity of the
selected equipment will be adequate to meet the cooling load.
Mastic
An
adhesive paste used in the fabrication and sealing of thermal insulation on
piping fittings, equipment, and duct work.
It spreads easily and dries permanently.
Its applications include new ducts and old, sheet metal seams, and ductboard.
Not all mastics are created equal.
Some are toxic, some are water-based, and some take longer to cure, making them
more suitable for new construction than retrofit.
Matched System
A
heating and cooling system comprised of products that have been certified to
perform at promised comfort and efficiency levels when used together, and used
according to design and engineering specifications.
Material Safety Data Sheets (MSDS)
Product
safety information sheets prepared by manufacturers and marketers of products
containing toxic chemicals.
These sheets can be obtained by requesting them from the manufacturer or
marketer.
Some stores, such as hardware stores, may have material safety data sheets on
hand for products they sell.
Mechanical System
See
HVAC.
Megawatt Hour (MWh)
One
thousand kilowatt-hours, or an amount of electricity that would supply the
monthly power needs of a typical home having an electric hot water system.
Megawatt (MW)
One
thousand kilowatts (1,000 kW) or one million (1,000,000) watts.
One megawatt is enough energy to power 1,000 average California homes.
MHPU (Mobile Home Package Unit)
The
Mobile Home Package Unit is an air conditioner with electric or gas heat or can
be a Heat Pump.
This unit has the condenser and air handler all-in-one package.
Commonly used in mobile homes and sits outside.
(Self-contained unit)
Microbiologicals
See
"Biological Contaminants."
Mildew
A
superficial covering of organic surfaces with fungi under damp conditions.
Mitigation
A
procedure or strategy aimed at reducing or eliminating an indoor air problem,
either through source control, ventilation control, exposure reduction, or air
cleaning.
Mixing Ratio (Relative Humidity)
Is
often used in drying applications and is the ratio of the mass of water vapor
to the mass of dry air with which it is associated.
Vaisala products give this output as grams of water per kilogram of dry air
(g/kg).
Mold
A
fungal infestation that causes disintegration of a substance.
Molds are a group of organisms that belong to the kingdom Fungi.
In this document, the terms fungi and mold are used interchangeably.
There are over 20,000 species of mold.
Multiple Chemical Sensitivity (MCS)
A
condition in which a person reports sensitivity or intolerance (as distinct
from "allergic") to a number of chemicals and other irritants at very
low concentrations.
mVOC
Microbial
volatile organic compound, a chemical made by a mold which may have a moldy or
musty odor.
Mycotoxin
A
metabolic product generated by certain fungi; includes both useful substances,
such as penicillin, and harmful substances, such as aflatoxin.
National Ambient Air Quality Standar (NAAQS)
The
US outdoor air quality standard designed to protect public health.
Pollutants covered by the NAAQS include ozone, sulfur dioxide, lead, nitrogen
dioxide, respirable particulates, and carbon monoxide.
National Institute for Occupational Safety and Health (NIOSH)
The
US government agency authorized to research and develop exposure criteria for
toxic substances and recommend these standards to OSHA.
NIOSH is also authorized to investigate unsafe working conditions.
Natural Ventilation
The
supply of outdoor air through passive flow from windows, chimneys, doors, and
other infiltration.
Negative Ion Generator
An
air cleaning device that uses static charges to remove particulates from indoor
air.
Negative Pressure
Condition
that exists when less air is supplied to a space than is exhausted from the space,
so the air pressure within that space is less than that in surrounding areas.
Under this condition, if an opening exists, air will flow from surrounding
areas into the negatively pressurized space.
NESHAP
National
Emissions Standard for Hazardous Pollutants
New
Construction
Energy
efficiency program promotion to encourage the building of new homes, buildings,
and plants to exceed standard government-mandated energy efficiency codes; it
may include major renovations of existing facilities.
Nitrogen dioxide (N02)
A
pollutant associated with combustion; a deep lung irritant.
The two most prevalent oxides of nitrogen are nitrogen dioxide (NO2) and nitric
oxide (NO).
Both are toxic gases with NO2 being a highly reactive oxidant, and corrosive.
NO gradually reacts with the oxygen in the air to form NO2.
Nozzle
An
air terminal device designed to generate a low energy loss and thus produce a
maximum throw by minimum entertainment.
Occupational Safety and Health Administration (OSHA)
The
regulatory arm of the US Department of Labor, which promulgates safety and
health standards, facilitates training programs, and enforces regulations on
work sites.
OSHA has developed permissible exposure limits for over 600 contaminants present
in the industrial workplace.
Ohm
A
unit of measure of electrical resistance.
One volt can produce a current of one ampere through a resistance of one ohm.
Organic Compounds
Chemicals
that contain carbon.
Volatile organic compounds vaporize at room temperature and pressure.
They are found in many indoor sources, including many common household products
and building materials.
Original Equipment Manufacturer (OEM)
Refers
to the manufacturers of complete vehicles or heavyÂduty engines, as contrasted
with remanufacturers, converters, retrofitters, up-fitters, and repowering or
rebuilding contractors who are overhauling engines, adapting or converting
vehicles or engines obtained from the OEMs, or exchanging or rebuilding engines
in existing vehicles.
Outdoor Air Supply
Air
brought into a building from the outdoors (often through the ventilation
system) that has not been previously circulated through the system.
Also known as "Make-Up Air."
Outdoor
Coil
[Also
see Condenser Coil] Refrigerant containing portion of a fan coil unit similar
to a car radiator, typically made of several rows of copper tubing with
aluminum fins.
Outside Air
Air
taken from outdoors and not previously circulated through the HVAC system.
Ozone (03)
A
kind of oxygen that has three atoms per molecule instead of the usual two.
Ozone is a poisonous gas, but the ozone layer in the upper atmosphere shields
life on earth from deadly ultraviolet radiation from space.
The molecule contains three oxygen atoms (O3).
a highly reactive form of oxygen.
Ozone exposure an result in mucous membrane irritation and potential pulmonary
damage.
Some copier machines and laser printers emit noticeable levels.
Ozone Generator
An
air cleaning device that produces highly reactive ozone, which reacts with
volatile organic compounds to form non hazardous products, remove particulates,
and reduce the number of biocontaminants.
These devices are controversial because their touted benefits may only be accomplished
at ozone levels above recommended exposure levels.
Ozone Hole
Thin
place in the ozone layer located in the stratosphere high above the Earth.
Stratospheric ozone thinning has been linked to destruction of stratospheric
ozone by CFCs and related chemicals.
The 1990 CLEAN AIR ACT has provisions to reduce and eliminate ozonedestroying
chemicals' production and use.
Ozone holes have been found above Antarctica and above Canada and northern
parts of the United States, as well as above northern Europe.
Package Unit or Package System
A
self-contained unit or system that has the Air Handler & Condenser in same
unit.
Normally placed outside the home and connected to a duct system by a
penetration through the homes foundation.
Except for geothermal which is a self-contained indoor unit that is place in a
closet, attached garage, basement, or mechanical room.
PAPR
Powered
air purifying respirator.
Particulates
Small
airborne particles found in indoor environments which include fibrous
materials, solid-state semi-volatile organic compounds, and biological
materials.
Pascals (Pa)
A
small unit of air pressure.
One pound per square inch equals 6,895 pascals.
Passive Smoking
The
inhalation of environmental tobacco smoke; also called involuntary smoking.
Pathogen
Any
microorganism or substance that causes disease.
PELs
Permissible
Exposure Limits (standards set by the Occupational, Saftey and Health
Administration).
Permeable
Porous,
allowing the passage of air.
Personal Protective Equipment (PPE)
Pesticides
Pesticides
are chemicals that are used to kill or control pests which include bacteria,
fungi, weeds, and other organisms, in addition to insects and rodents.
Most pesticides are inherently toxic.
Most contain volatile organic compounds.
Picocurie
A
unit of measurement used to describe radon concentration.
Plenum
Air
compartment connected to a duct or ducts.
Air flow passage made of duct board, metal, drywall, or wood.
Joins supply and return ducts with HVAC equipment.
The portions of the air distribution system that makes use of the building
structure, and the sheet meal that connects distribution ductwork to an air
handling unit.
Many buildings use the space above a dropped ceiling as a plenum.
Pollutant Pathways
Avenues
for distribution of pollutants in a building.
HVAC systems are the primary pathways in most buildings; however all building
components interact to affect how air movement distributes pollutants.
Positive Pressure
Condition
that exists when more air is supplied to a space than is exhausted, so the air
pressure within that space is greater than that in surrounding areas.
Under this condition, if an opening exists, air will flow from the positively
pressurized space, outward to surrounding areas.
Power
The
rate at which energy is transferred.
Electricity for use as energy is also referred to as power.
Electrical power is usually measured in watts.
Also used for a measurement of capacity.
PPM (Parts Per Million)
A
unit, which may be mass/mass, and hence represents a direct measure of
fractional mass, or volume/volume, and represents in this case, a molar
fraction at low pressures and high temperatures, commonly used to represent the
degree of pollutant concentration where the concentrations are small.
Pressed Wood Products
A
group of materials used in building and furniture construction that are made
from wood veneers, particles, or fibers bonded together with an adhesive under
heat and pressure.
Pressure balancing
The
process of neutralizing pressure differences within a home.
Preventive Maintenance (PM)
A
program of building maintenance implemented to reduce the possibility of
problems, usually through periodic inspection, cleaning, adjustment.
calibration.
and replacement of functioning, parts of the HVAC system, as well as
housekeeping practices to reduce the buildup of potential contaminants.
Primarily done on a building's mechanical systems, this involves a regular and
systematic inspection, cleaning, and replacement of worn parts, materials, and
systems.
Preventive maintenance helps to prevent parts, material, and systems failure by
ensuring that parts, materials and systems are in good working order.
Price of Quality, The
There
is more to buying a heat pump or air conditioner than ratings.
The quality of construction and materials used as well as the reliability of
the manufacturer and installing contractor can all affect your long-term satisfaction
and comfort.
Top quality, high efficiency equipment will cost more initially, but it will
save you money on utility bills and service calls for years to come.
Be sure to weigh all the factors before choosing your new system.
Primary Air Flow Rate
Volume
of air entering a supply air terminal device within a time unit.
Process Heating
Energy
Efficiency program promotion of increased electric energy efficiency
applications in industrial process heating.
Programmable Controller
A
device that controls the operation of electrical equipment (such as air
conditioning units and lights) according to a preset time schedule.
Psychosocial Factors
Psychological,
organizational, and personal stressors that could produce symptoms similar to
those caused by poor indoor air quality.
R-Value
A
measure, in Btu/(ft2 F), of the resistance to transmission of heat by an
insulating material.
The higher the R-value of a material, the greater is its insulating properties
and the slower the heat flow through it.
The specific value needed to insulate a home depends on climate, type of
heating system and other factors.
Radiant
System
that uses hot surfaces to radiate or convect heat into the environment.
Without the use of fans or blowers
Radiant
Barrier
A
device designed to reduce or stop the flow of radiant energy.
Radiation
The
transfer of heat directly from one surface to another (without heating the
intermediate air acting as a transfer mechanism).
Radioactive Decay
The
disintegration of the nuclei of the atoms of radioactive (charged) elements
with the concomitant release of alpha, beta, or gamma rays.
Radon (Rn) and Radon Decay Products
Radon
is a radioactive gas formed and emitted by the decay of radium and uranium in
rock.
The radon decay products (also called radon daughters or progeny) can be
breathed into the lung where they continue to release radiation as they further
decay.
Re-Entrainment
Situation
that occurs when the air being exhausted from a building is immediately brought
back into the system through the air intake and other openings in the building
envelope.
Receiver
Tank
on the liquid side of a system that holds excess refrigerant in the system that
needs to be there for proper operation.
Reclaiming
Processing
or returning used refrigerant to the manufacturer or processor for disposal or
reuse.
Recool
The
sensible cooling of air that has been previously heated by HVAC systems serving
the same building.
Refrigerant
Substance
used in refrigerating mechanism.
A substance that produces a refrigerating effect while expanding or vaporizing.
Air conditioning systems use Refrigerant in the Evaporator Coil to cool air as
it passes by.
Refrigerants absorb heat in evaporator by change of state from a liquid to a
gas, and releases its heat in a condenser as the substance returns from the
gaseous state back to a liquid state.
Refrigerant Charge
The
amount of refrigerant contained within the airc conditioning equipment and
required for proper operation.
Refrigerant Lines
Two
copper lines that connect the Condenser (Outdoor) Coil to the Evaporator
(Indoor) Coil.
Registers
Combination
grille and damper assembly covering an air opening or end of an air duct.
Coverings for the ducts where they open to the conditioned space.
(Same as Grilles)
Reheat
The
heating of air that has been previously cooled either by mechanical
refrigeration or economizer cooling systems.
Relative Humidity (RH)
Relative
humidity is defined as the ratio of the water vapor pressure to the saturation
vapor pressure (over water) at the temperature of the gas.
RH = Pw/Pws * 100
Relative
Risk
The
ratio of health impact incidence among exposed individuals to incidence among
unexposed individuals.
RELs
Recommended
Exposure Limits (recommendations made by the National Institute for
Occupational Safety and Health (NIOSH)).
Remediate
Fix
Reservoir
The
environmental substrate, or source, of a particular organism.
Reservoirs for indoor biocontaminants include stagnant water, moist surfaces,
and dust collection sites.
Residential
The
residential sector is defined as private household establishments which consume
energy primarily for space heating, water heating, air conditioning, lighting,
refrigeration, cooking, and clothes drying.
The classification of an individual consumer¹s account, where the use is both
residential and commercial, is based on principal use.
Resistance (Electrical)
The
ability of all conductors of electricity to resist the flow of current, turning
some of it into heat.
Resistance depends on the cross section of the conductor (the smaller the cross
section, the greater the resistance), the material, the length of the flow
path, and its temperature (the hotter the cross section, the greater its
resistance).
Resistance (Thermal)
The
reciprocal of thermal conductance.
See R-VALUE.
Respirable Suspended Particulates
Particulates
less than 10 µm in diameter that can enter the respiratory tract.
Retrofit
Broad
term that applies to any change after the original purchase, such as adding
equipment not a part of the original purchase.
As applied to alternative fuel vehicles, it refers to conversion devices or
kits for conventional fuel vehicles.
(Same as 3aftermarket2.)
Return
The
ductwork that carries air from the house to the air handler.
Return Air
Air
drawn into a heating unit after having been circulated from the heater's output
supply to a room.
The air removed from an occupied space and returned to the air handler to be
exhausted or recirculated.
RSES
A
leading HVAC/R Association - Refrigeration Service Engineers Society - http://www.rses.org/
Saturation
Temperature
Also
referred to as the boiling point or the condensing temperature.
This is the temperature at which a refrigerant will change state from a liquid
to a vapor or visa versa.
SEER (Seasonal Energy Efficiency Ratio)
An
efficiency measurement that is similar to Miles Per Gallon for cars.
The higher this number, the more energy efficient they system is.
The amount of cooling your equipment delivers per every dollar spent on
electricity.
The higher the number the lower the operating cost (not more cooling.) SEER
applies to air conditioners and heat pumps.
In the past, a unit with a SEER of 8.00 was considered standard efficiency, and
a unit with a 10.00 SEER was considered high efficiency.
After January 1, 1992, the minimum SEER required by the DOE is 10.00 and 15.00+
SEER is considered high efficiency.
EER & SEER can not be compared equally.
Air source equipment is rated by SEER and geothermal equipment is rated by EER.
New units have SEER ratings from 10 to 17 BTUs per watt.
The total cooling of a central unitary air conditioner or unitary heat pump in
Btu's during its normal annual usage period for cooling divided by the total
electric energy input in watt-hours during the same period.
The Seasonal Energy Efficiency Ratio is a standard method of rating air
conditioners based on three tests.
All three tests are run at 80 degrees Fahrenheit inside and 82 degrees
Fahrenheit outside.
The first test is run with humid indoor conditions, the second with dry indoor
conditions, and the third with dry conditions cycling the air conditioner on
for 6 minutes and off for 24 minutes.
The published SEER may not represent the actual seasonal energy efficiency of
an air conditioner in your climate.
The total cooling output of a central air conditioning unit in Btus during its
normal usage period for cooling divided by the total electrical energy input in
watt-hours during the same period, as determined using specified federal test
procedures.
[Title 20, Section 2-1602(c)(11)].
Sensible Cooling Load
The
heat gain of the home due to conduction, solar radiation, infiltration,
appliances, people, and pets.
Burning a light bulb, for example, adds only sensible load to the house.
This sensible load raises the dry-bulb temperature.
Sensible Heat
Heat,
that when added or removed, causes a change in temperature but not in state.
Heat that results in a temperature change.
Sensitization
Repeated
or single exposure to an allergen that results in the exposed individual
becoming hypersensitive to the allergen.
Setback
A
reduction of climate control energy demand in HVAC controls when a building is
unoccupied.
Setpoint
The
temperature to which a thermostat is set to result in a desired heated space
temperature.
Short-Circuiting
Situation
that occurs when the supply air flows to return or exhaust grilles before
entering the breathing zone (area of a room where people are).
To avoid short-circuiting, the supply air must be delivered at a temperature
and velocity that results in mixing throughout the space.
Sick building
A
building in which the indoor air quality is considered to be unacceptable to a
substantial majority of occupants.
Sick Building Syndrome (SBS)
A
phenomenon in which building occupants experience a variety of health and/or
comfort effects linked to time spent in a particular building, but where no
specific illness or causative agent can be identified.
Symptoms in sufferers often include headaches, eye irritation, and respiratory
irritation.
Term that refers to a set of symptoms that affect some number of building
occupants during the time they spend in the building and diminish or go away
altogether during periods when they leave the building.
(Contrast with Building Related Illness.)
Single
Package
A
year 'round heating and air conditioning system that has all the components
completely encased in one unit outside the home.
Sizing
Refers
to the procedure a heating contractor goes through to determine how large a
furnace (measured in btuh) is needed to heat a house efficiently.
Too small a furnace won't deliver enough heating; too large a furnace increases
energy costs and can have an adverse effect on comfort.
Sizing depends on the square-footage of the home, the amount of ceiling and
wall insulation, the window area, use of storm doors, storm windows, and more.
Smoke stick
A
diagnostic tool used to observe air flow.
Usually it consists of a chemical in a squeezable container.
When squeezed it emits smoke which visibly follows air flow currents.
Sound Attenuators
Components
which are inserted into the air distribution system and designed to reduce
airborne noise which is propagated along the ducts.
Sound Rating Number (SRN)
Sound
is measured in bels (a bel equals 10 decibels).
The SRN of a unit is based on ARI test, performed at ARI standard rating
conditions.
Average sound rating range from 7.0 to 8.0 decibels.
The lower the SRN rating, the quieter the unit.
Sound Ratings
Although
sound does not affect the efficiency of a unit, it will certainly affect your
comfort.
If your unit has a low sound level, you will hardly notice it is operating.
But if it has a higher sound level, it may mean your good night's sleep is
disturbed every time it runs!
Source
Control
A
preventive strategy for reducing airborne contaminant levels through removal of
the material or activity generating the pollutants.
Sources
Sources
of indoor air pollutants.
Indoor air pollutants can originate within the building or be drawn in from outdoors.
Common sources include people, fixtures and furnishings, photocopiers, plants,
food, etc.
Specific Heat
In
English units, the quantity of heat, in Btu, needed to raise the temperature of
one pound of material one degree Fahrenheit.
Split System
Refrigeration
or air conditioning installation, which places condensing unit outside or away
from evaporator.
These unit are connected together by a supply and return refrigerant lines.
Also applicable to heat pump installations.
A combination heat pump or air conditioner with indoor components such as a
furnace or blower coil.
To maximize effectiveness, Split Systems should be matched.
Spore
Molds
reproduce by means of spores.
Spores are microscopic; they vary in shape and size (2-100 micrometers).
Spores may travel in several ways--they may be passively moved (by a breeze or
waterdrop), mechanically disturbed (by a person or animal passing by), or
actively discharged by the mold (usually under moist conditions or high
humidity).
Spread (LS) (for a supply air terminal device)
Maximum
distance between two vertical planes tangent to a specified envelope and
perpendicular to a plane through the core center.
The spread are generally referred to the envelope corresponding to 0.25 m/s for
zero supply temperature differential (i.e., under isothermal conditions).
SRN (Sound Rating Number)
Sound
is measured in bels (a bel equals 10 decibels).
The SRN of a unit is based on ARI test, performed at ARI standard rating
conditions.
Average sound rating range from 7.0 to 8.0 decibels.
The lower the SRN rating, the quieter the unit.
SRN (Sound Rating Number )
Sound
is measured in bels (a bel equals 10 decibels).
The SRN of a unit is based on ARI test, performed at ARI standard rating
conditions.
Average sound rating range from 7.0 to 8.0 decibels.
The lower the SRN rating, the quieter the unit.
Stack effect
A
condition resulting from the rise of heated air, which creates positive
pressure near the top of the building and negative pressure toward the bottom.
Stack effect pressures have been known to overpower mechanical ventilation
systems, disrupting proper circulation and contributing to the infiltration and
stagnation of pollutants.
Stack Effect
The
overall upward movement of air inside a building that results from heated air
rising and escaping through openings in the building super structure, thus
causing an indoor pressure level lower than that in the soil gas beneath or
surrounding the building foundation.
Standard Industrial Classification (SIC)
A
set of codes developed by the Office of Management and Budget, which
categorizes business into groups with similar economic activities.
Static Pressure
Condition
that exists when an equal amount of air is supplied to and exhausted from a
space.
At static pressure, equilibrium has been reached.
Statistical Significance
The
probability that and degree to which the results of an experimental study
describe an actual relationship between two factors beyond that which might be
expected by pure coincidence.
Straight Cool
This
is an air conditioner that uses different forms of heating such as Natural Gas,
LP Gas, Electric Resistance heat and oil.
Stratosphere
Part
of the atmosphere, the gases that encircle the Earth.
The stratosphere is a layer of the atmosphere 9-31 miles above the Earth.
Ozone in the stratosphere filters out harmful sun rays, including a type of
sunlight called ultraviolet B, which has been linked to health and environmental
damage.
Subcooled Liquid
Liquid
refrigerant which is cooled below its saturation temperature.
Superheated Vapor
Refrigerant
vapor which is heated above its saturation temperature.
If a refrigerant is superheated, there is no liquid present.
Supplementary Heat (Emergency Heat)
The
auxiliary or emergency heat provided at temperatures below a heat pump's
balance point.
It is usually electrical resistance heat.
Supply
The
ductwork that carries air from the air handler to the rooms in the house.
Supply Air
The
air flow entering the treated space.
Swamp Cooler
See
Evaporative Cooler.
Switchover Valve
A
device in a heat pump that reverses the flow of refrigerant as the system is
switched from cooling to heating.
Also called a reversing valve or four-way valve.
System
A
combination of equipment and/or controls, accessories, interconnecting means
and terminal elements by which energy is transformed to perform a specific
function, such as climate control, service water heating, or lighting.
Systems Control
The
control of indoor air pollutants through the use of mechanical means such as
ventilation control or air cleaning.
Temperature
Degree
of hotness or coldness measured on one of several arbitrary scales based on
some observable phenomenon (such as the expansion).
Temperature Differential
The
difference between the entering and leaving temperature for a given fluid.
For example, a 10-degree evaporator temperature differential for a chiller
would describe an operating condition where the entering water temperature is
54 degrees and the leaving is 44 degrees.
Testing, Adjusting, And Balancing (TAB)
The
diagnostic and corrective procedures for HVAC controls and operating components
to ensure provision of specified airflow rates and environmental conditions.
Therm
Another
measurement of heat.
One therm equals One hundred thousand (100,000) British thermal units (1 therm
= 100,000 Btu).
Thermal (Energy) Storage
A
technology that lowers the amount of electricity needed for comfort
conditioning during utility peak load periods.
A buildings thermal energy storage system might, for example, use off-peak
power to make ice or to chill water at night, later using the ice or chilled
water in a power saving process for cooling during the day.
See THERMAL MASS.
Thermal Mass
A
material used to store heat, thereby slowing the temperature variation within a
space.
Typical thermal mass materials include concrete, brick, masonry, tile and
mortar, water, and rock or other materials with high heat capacity.
Thermodynamics
The
study of the transformation of energy into other manifested forms and of their
practical applications.
Commonly encountered forms of the statements of the three principal laws of
thermodynamics are: (0) The heat capacity and entropy of every crystalline
solid becomes zero at absolute zero (0 degrees Kelvin).
(1) The Law of the Conservation of Energy -- energy may be transformed in an
isolated system, but its total is constant.
(2) Heat from a reservoir at a constant temperature cannot be changed
completely into work by a cyclic process.
Thermostat
A
temperature sensitive switch for controlling the operation of a heater or
furnace.
Typically found on a wall inside the home, that consists of a series of sensors
and relays that monitor and control the functions of a heating and cooling
system.
A device that allows you to control the temperature inside your home by telling
the heating or cooling system how much air to produce.
An automatic control device designed to be responsive to temperature and
typically used to maintain set temperatures by cycling the HVAC system.
Thermostat, Air-Sensing
Thermostat
unit in which sensing element is located in refrigerated space.
Thermostat, Setback (Programmable Thermostat)
A
state-of-the-art electronic thermostat with a built-in memory that can be
programmed for different temperature settings at different times of the day.
A device, containing a clock mechanism, which can automatically change the
inside temperature maintained by the HVAC system according to a preset schedule.
The heating or cooling requirements can be reduced when a building is
unoccupied or when occupants are asleep.
Threshold (IAQ)
The
contaminant dose or exposure level below which there is no expected significant
effect.
Threshold Limit Value (TLV)
The
American Conference of Governmental Industrial Hygienists recommended guideline
for exposure limit represented in terms of exposure over a work day (8 hours)
or a work week (40 hours).
Threshold Limit Values (TLVs)
Threshold
Limit Values (guidelines recommended by the American Conference of Governmental
Industrial Hygenists).
Throw (Lt)
The
maximum distance between the center of the core and a plane which is tangent to
a specified envelope and perpendicular to the intended direction of flow The
throw is generally referred to as the envelope corresponding to 0.25 m/s for
zero supply temperature differential (i.e., under isothermal conditions).
Tight Building Syndrome (TBS)
A
condition in which a building is very tightly insulated against infiltration,
its ventilation is reduced for energy conservation, and airborne contaminants
are sufficiently elevated to cause health effects in occupants; often used
synonymously with sick building syndrome (SBS).
Time Delay
Usually
refers to a device that will not allow the condenser to restart for an average
of 5 minutes.
Ton or "Ton of Cooling"
A
cooling unit of measure.
Each ton equals the cooling effect of 12,000 Btuh.
Heat pumps and air conditioners are generally sized in tons.
Typical sizes for single family residences are between two and five tons.
It is important to note that actual capacity is not constant and will change
based on outdoor or indoor temperatures.
The published capacity rating of air conditioners and heat pumps is based on
performance at the ARI standard temperature levels of 95 F outside, 80 F
inside, and 50% relative humidity.
The number of tons a system has is the total BTU capacity of the system.
The size of the area to be cooled will determine the correct size of the system
in tons.
While an air conditioner may be called a three ton unit, it may not produce
36,000 Btu/h in cooling.
There is a wide variety of actual capacities that are called "three
tons."
Total
air flow rate (QL)
Sum
of the primary and secondary air flow rates which are moved in the treated
space.
Total Home Comfort System
The
ultimate solution to providing you with consistent, customized home comfort,
despite the ever-changing weather.
Total Volatile Organic Compounds (TVOCs)
A
measure representing the sum of all VOCs present in the air to provide an
approximate indication of pollutant levels.
Indoor air typically contains hundreds of different VOCs in very low
concentrations, some of which can have additive effects.
Total Volatile Organic Compounds (TVOCs)
Total
volatile organic compounds.
See "Volatile Organic Compounds (VOCs)"
Toxicant
A
substance that can cause tissue damage or otherwise affect organs or systems
within the body.
Tracer Gas
An
inert compound that is a rare constituent of indoor air which is released into
building air and monitored qualitatively and/or quantitatively to characterize
airflow characteristics to determine air pathways, infiltration, and
ventilation efficiency measurements.
Tracer Gases
Compounds,
such as sulfur hexaflouride, which are used to identify suspected pollutant
pathways and to quantify ventilation rates.
Trace gases may be detected qualitivatively by their odor or quantitatively by
air monitoring equipment.
Transformer
A
device, which through electromagnetic induction but without the use of moving
parts, transforms alternating or intermittent electric energy in one circuit
into energy of similar type in another circuit, commonly with altered values of
voltage and current.
Transmittance
The
time rate of heat flow per unit area under steady conditions from the air (or
other fluid) on the warm side of a barrier to the air (or fluid) on the cool
side, per unit temperature difference between the two sides.
UA
A
measure of the amount of heat that would be transferred through a given surface
or enclosure (such as a building envelope) with a one degree temperature
difference between the two sides.
The UA is calculated by multiplying the U-Value, or overall heat transfer
coefficient U, by the area A of the surface (or surfaces).
Unconditioned Space
A
space that is neither directly nor indirectly conditioned space, which can be
isolated from conditioned space by partitions and/or closeable doors.
Upflow
See
"Upflow Furnace"
Upflow
Furnace
A
furnace that pulls cool return air in from the bottom and blows/expels warm air
out the top into the duct work.
This type of furnace is usually installed in a basement or an out-of-the-way
closet.
Urea Formaldehyde Foam Insulation (UFFI)
A
form of insulation no longer in use because of excessive formaldehyde emissions
and documented associated health impacts.
Useful Thermal Output
The
thermal energy made available for use in any industrial or commercial process,
or used in any heating or cooling application, i.e., total thermal energy made
available for processes and applications other than electrical generation.
Valves
Components
inserted into air ducts or devices which permit modification of the air
resistance of the system and consequently a complete shut-off of the air flow
(control valves).
VAV System (Variable Air Volume System)
A
mechanical HVAC system capable of serving multiple zones which controls the
temperature maintained in a zone by controlling the amount of heated or cooled
air supplied to the zone.
VAV (Variable Air Volume)
Variable
Air Volume.
Ventilation
The
process of supplying or removing air by natural or mechanical means to or from
any space.
Such air may or may not have been conditioned or treated.
Ventilation Air
Defined
as the total air, which is a combination of the air brought inside from
outdoors and the air that is being recirculated within the building.
Ventilation effectiveness
A
measure of the fraction or percentage of outdoor air that reaches the occupied
zone of a specified area; an evaluation of air delivery to occupants,
regardless of the effectiveness of contaminant removal.
Ventilation efficiency
An
evaluation of the pollutant removal capacity of a ventilation system.
Ventilation Rate
The
rate at which indoor air enters and leaves a building.
Expressed in one of two ways: the number of changes of outdoor air per unit of
time (air changes per hour, or "ach") or the rate at which a volume
of outdoor air enters per unit of time (cubic feet per minute, or
"cfm").
Ventilation standard
A
specification for the minimum rate of input of outdoor air into indoor spaces.
VFD (Variable Frequency Drive)
Electronic
speed control for motors.
Volatile Organic Compounds (VOCs)
One
of a class of chemical compounds; indoor sources include tobacco smoke,
building products, furnishings, cleaning materials, solvents, and office
supplies.
In sufficient quantities, VOCs can cause eye, nose, and throat irritations;
dizziness; and headaches.
Some VOCs are suspected carcinogens.
Data for health effects resulting, from exposure to the characteristically low
levels of VOCs in the indoor environment are scarce.
Compounds that vaporize (become a gas) at room temperature.
Common sources which may emit VOCs into indoor air include housekeeping and
maintenance products, and building and furnishing materials.
In sufficient quantities, VOCs can cause eye, nose, and throat irritations,
headaches, dizziness, visual disorders, memory impairment; some are known to
cause cancer in animals; some are suspected of causing, or are known to cause,
cancer in humans.
Volt
A
unit of electromotive force.
It is the amount of force required to drive a steady current of one ampere
through a resistance of one ohm.
Electrical systems of most homes and office have 120 volts.
W (Watt)
A
watt is a unit of electricity.
A unit of measure of electric power at a point in time, as capacity or demand.
It is the rate of energy transfer equivalent to 1 ampere flowing under a
pressure of 1 volt at unity power factor.
One watt of power maintained over time is equal to one joule per second.
Some Christmas tree lights use one watt.
The watt is named after Scottish inventor James Watt and is capitalized when
shortened to w and used with other abbreviations, as in kWh.
Water vapor
Water
vapor can be treated as a gas.
At a particular temperature air for example can only hold so much water vapor.
The higher the temperature the more water vapor it can hold.
When saturated the relative humidity would be 100 % RH, so relative humidity
describes how close to saturation the air is.
It is important to remember that in a process with a high relative humidity a
small drop in temperature will cause the humidity to rise and the environment
to saturate.
Rapid temperature changes in a an environmental chamber for example could also
cause condensation.
Watt-Hour (W-hr)
One
watt of power expended for one hour.
An electrical energy unit of measure equal to 1 watt of power supplied to, or
taken from, an electric circuit steadily for 1 hour.
One thousandth of a kilowatt-hour.
WB
Wet
Bulb
WC
(Water Column)
Common
measure of air pressure used in HVAC systems.
Weather Stripping
Specially
designed strips, seals and gaskets installed around doors and windows to limit
air leakage.
Wet Bulb Temperature
The
temperature at which water, by evaporating into air, can bring the air to
saturation at the same temperature.
Wet-bulb temperature is measured by a wet-bulb psychrometer.
Traditionally this was the temperature indicated by a thermometer whose bulb is
wrapped in a wet sheath.
The wet bulb temperature and the dry bulb temperature (i.e air temperature)
would then be used to calculate relative humidity or dewpoint.
Alternatively charts or tables can be used.
Wet-bulb Temperature
When
a wet wick is placed over a standard thermometer and air is blown across the
surface, the water evaporates and cools the thermometer below the dry-bulb
temperature.
This cooler temperature (called the wet-bulb temperature) depends on how much
moisture is in the air.
Whole House Fan
A
system capable of cooling a house by exhausting a large volume of warm air when
the outside air is cool.
Zonal Control
A
method of designing and controlling the HVAC system of a residence so that
living areas can be maintained at a different temperature than sleeping areas
using independent setback thermostats.
If specific requirements are met, zonal control may earn a credit towards
compliance with whatever building energy efficiency standards are applicable.
Zone
1)
Conditioned space in a house under the control of a thermostat.
2) A space within a house with a distinct pressure compared to other pressure
zones.
Also see Buffer zone.
or 1) In the context of an HVAC system: a space or group of spaces served by an
HVAC system or portion of an HVAC system controlled by a single thermostat or
other control device; 2) A space or group of spaces within a building with
sufficiently similar comfort conditioning requirements so that comfort
conditions can be maintained throughout by a single control device.
Zone Heat
A
central heating system in a building, designed to allow different temperatures
to be maintained in two or more parts of the building.
Zoning
A system in which living areas or groups of rooms
are divided into separate spaces and each space's heating/air conditioning is
controlled independently.
This can be accomplished by using either multiple independent systems, or a
single system using electronic controls and motorized dampers (see Damper).
For example, you might prefer to have the kitchen area of your home be slightly
cool, while at the same time keeping the temperature in the bedrooms warmer.